Appendix b: troubleshooting, Software – Sensaphone IMS-1000 Users manual User Manual

Page 105

Advertising
background image

Appendix B: Troubleshooting

105

Appendix B: Troubleshooting

Software

Why does my IMS-1000 begin dialing as soon as I turn it on?
n

IMS-1000 will only dial to deliver an alarm message. An unacknowledged alarm exists, and IMS-1000 is

trying to deliver an alarm message.

Why can’t I connect with my IMS-1000 using my Ethernet network?
n

The IMS-1000’s network settings may be incorrect. Verify the IP address, Gateway, DNS, and Subnet mask

settings.

n

There may be a network IP address conflict. The IMS-1000’s IP address may be the same as another device

on your network.

Will IMS-1000 retain its programming if there has been a long power failure and the backup

battery dies?
Yes. When all power is removed from the IMS-1000,voice messages and unit programming are retained in a
nonvolatile solid-state flash disk.

My IMS-1000 unit got damaged and had to be replaced. Can I use the original unit’s saved

programming to quickly program the replacement unit?
Yes.

Why won’t my IMS-1000 dial out?
n

Check that you have a Touch-Tone telephone line. The IMS-1000 will not be able to dial out if it’s on a

Pulse telephone line or a digital extension from a telephone system.

n

The Contact telephone number may be incorrectly programmed. Verify the telephone numbers. Is a

‘1 +area code’ prefix required? Does your telephone line require a ‘9’ prefix to reach an outside line?

n

Recognition time may be set too long for an alarm condition to become a valid alarm. Shorten the

Recognition time for the alarm or increase the amount of time that the monitored condition exists.

n

‘Dial Out Attempts’ might be set to zero. If this is the case, the IMS-1000 will make zero attempts to call

the programmed Contacts. Increase ‘Dial Out Attempts’ to a number greater than zero.

I keep getting a busy signal when I call my IMS-1000 .
The IMS-1000 may be trying to deliver an alarm message.

Why does IMS-1000 call again with the same alarm after I just acknowledged it?
n

The alarm is clearing and quickly re-tripping. If this occurs, and the Alarm Recognition time is very short,

the result will be another call for the re-tripped alarm. Increase the Alarm Recognition time to avoid rapid
callbacks for the same alarm.

Advertising