Chapter 5: IMS-1000 Sensors

87

IMS-4850 Dry Contact Bridge

Installation Instructions

Introduction

The IMS-1000 Dry Contact Bridge allows you to connect
a dry contact alarm from any device to your IMS-1000.
The Dry Contact Bridge is compatible with Normally
Open and Normally Closed contacts. The electrical con-
nection between the sensor and IMS-1000 is made via
RJ-45 patch cable (not included). The sensor may be
mounted either on a wall or rest on the floor.

Package Contents
(1) IMS-4850 Dry Contact Bridge
(2) Plastic drywall anchors
(2) #6 Metal tapping screws
(4) Rubber feet

Wiring the Contact

Connect your alarm contact to the terminal block labeled Input. Insert

1

/

2

" stripped bare wire into

the slot and tighten the screw. The slide switch selects between Normally Open (NO) and Normally
Closed NC) dry contacts. Place the switch in the appropriate position for the alarm contact you are
monitoring.

Figure 1: Connections to the IMS-4850

Cabling

The Dry Contact Bridge connects to the IMS-1000 via an RJ-45 cable (e.g. CAT5 cable). The
connection from the sensor to the IMS-1000 can utilize your existing network wiring infrastructure.
For example, the sensor may be installed in another room or another floor. Connect the bridge to
your structured wiring network via an RJ-45 jack. At the other end, connect a patch cable from
your structured wiring patch panel directly to the IMS-1000 environment input.