Ims-4862 smoke detector sensor, Installation instructions – Sensaphone IMS-1000 Users manual User Manual

Page 99

Advertising
background image

Chapter 5: IMS-1000 Sensors

99

IMS-4862 Smoke Detector Sensor

Installation Instructions

Introduction

The IMS-4862 Smoke Detector Sensor is designed to
connect to the IMS-1000 and monitor for smoke in
indoor environments. The electrical connection between
the sensor and IMS-1000 is made via the attached RJ-45
patch cable. The sensor may be secured to a wall or
ceiling (hardware not included).

Cabling

The Smoke Detector Sensor comes with an attached 7' cable with an RJ-45 plug on the end. If the
sensor is close to the IMS-1000, you can plug the sensor directly to an IMS environmental input.
If the cable is too short you can use the included RJ-45 adaptor and a longer patch cable to extend
the length. For applications where the sensor may be far from the IMS unit, you may utilize your
existing network wiring infrastructure. For example, the sensor may be installed in another room or
another floor. Connect the sensor to your structured wiring network via an RJ-45 jack. At the other
end, connect a patch cable from your structured wiring patch panel directly to the IMS-1000 envi-
ronment input.

Caution: The IMS sensors are not TCP/IP devices and therefore should not be
connected directly to any wiring infrastructure that is connected to network equipment
such as a hub, router, or switch. Sensors use RJ-45 plugs and cables similar to those
used with Ethernet devices.

Mounting

The sensor may be mounted directly against a wall or ceiling (hardware not included).

Configuration

All IMS Solution sensors are auto-configured when you plug them into the IMS-1000. When a
new sensor is plugged into the IMS-1000, the configuration is set to the factory default via the
Sensor Template.

If you have modified these templates, the configuration will be set to the modi-

fied configuration. When a sensor is removed, or the connection is disrupted, the configuration
data remains intact but the sensor will go into trouble status and generate a trouble alarm. When
the sensor is plugged in again, or the connection is re-established, configuration data remains
unchanged and the sensor returns to normal operating condition.
The smoke alarm is a latching alarm device. To reset the smoke alarm, momentarily disconnect the
cable from the front panel of the IMS-1000 and then reconnect it.

Caution: Removing a sensor for less than 60 seconds does not produce a trouble alarm.
Removing or unplugging a sensor for more than 60 seconds or plugging in a different
sensor at any time will cause a trouble alarm.

Advertising