Configuration, Fahrenheit/celsius selection – Sensaphone IMS-1000 Users manual User Manual

Page 58

Advertising
background image

IMS-1000 Manual

58

J2

Deg C

Deg F

Figure 2: 4810 with Cable exiting out enclosure bottom

Configuration

All IMS Solution sensors are auto-configured when you plug them into the IMS-1000. When a
new sensor is plugged into the IMS-1000, the configuration is set to the factory default via the
Sensor Template.

If you have modified these templates, the configuration will be set to the modi-

fied configuration. When a sensor is removed, or the connection is disrupted, the configuration
data remains intact but the sensor will go into trouble status and generate a trouble alarm. When
the sensor is plugged in again, or the connection is re-established, configuration data remains
unchanged and the sensor returns to normal operating condition.

Caution: Removing a sensor for less than 60 seconds does not produce a trouble alarm.
Removing or unplugging a sensor for more than 60 seconds or plugging in a different
sensor at any time will cause a trouble alarm.

Fahrenheit/Celsius Selection

The IMS-4810 can provide temperature readings in either degrees Fahrenheit or Celsius. To select
one or the other, remove the sensor cover by turning the two hex screws on the bottom of the sen-
sor housing clockwise. Locate the black jumper (see Figure 3) marked J2. Install the jumper in the
“Deg F” position for Fahrenheit or the “Deg C” position for Celsius. Secure the sensor cover by
turning the two hex screws on the bottom of the cover counterclockwise.

J2

Deg C

Deg F

Figure 3: Jumper location (set for Degrees Celsius)

Advertising