Sensaphone IMS-1000 Users manual User Manual

Page 72

Advertising
background image

IMS-1000 Manual

72

Configuration

All IMS Solution sensors are auto-configured when you plug them into the IMS-1000. When a
new sensor is plugged into the IMS-1000, the configuration is set to the factory default via the
Sensor Template. If you have modified these templates, the configuration will be set to the modi-
fied configuration. When a sensor is removed, or the connection is disrupted, the configuration
data remains intact but the sensor will go into trouble status and generate a trouble alarm. When
the sensor is plugged in again, or the connection is re-established, configuration data remains
unchanged and the sensor returns to normal operating condition.

Caution: Removing a sensor for less than 60 seconds does not produce a trouble alarm.
Removing or unplugging a sensor for more than 60 seconds or plugging in a different sen-
sor at any time will cause a trouble alarm.

Sensor Template (factory default)

Input Name:

Humidity

Low Limit:

20%

High Limit:

60%

Recognition Time:

60 Seconds

Reset Time:

0 Seconds

Data Logging:

Active

Voice: humidity.wav

Input Class:

Humidity

Specifications

Range: 0–100% RH

Temperature: 32–122º F (0–50º C)

Accuracy:

+/- 5%

Connector:

RJ-45

Housing:

white plastic