Installation and configuration, Physical description, Front panel layout – Sensaphone IMS-1000 Users manual User Manual

Page 17: Rj-45 10/100base-t ethernet port, Phone jack (optional), Sensor inputs, Ims-1000, Chapter 1: installation 17

Advertising
background image

Chapter 1: Installation

17

INSTALLATION and CONFIGURATION

Physical Description

The IMS-1000 is housed in a 14"w x 1.75"h x 7"d enclosure, which is 1 EIA rack-mount space
high.

Front Panel Layout

The front panel contains connections for eight sensor inputs, Ethernet port, and status LEDs. See
figure below:

SENSAPHONE

®

System On

Battery Ok

Output On

Alarm

Output

Ethernet Expansion

Phone

E n v i r o n m e n t a l S e n s o r I n p u t s

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

REMOTE MONITORING SYSTEM

IMS-1000

Infrastructure Monitoring System

SENSAPHONE

®

1

2

3

4

5

6

Figure 1: Front Panel Layout of the IMS-1000

1 Phone Line (not present on model IMS-1001)
2 Ethernet port (10/100Base-T)
3 USB Expansion Port
4 Sensor Inputs (8)
5 Output
6 LED

RJ-45 10/100BASE-T Ethernet Port

This jack is for connecting to your network so that the IMS-1000 can send e-mail, display it’s web
page and ping selected network servers and/or services. Two LEDs indicate received data (green)
and transmitted data (yellow).

Phone Jack (optional)

Connect the IMS-1000’s Phone jack to a standard 2-wire analog phone line. The unit dials using
touch-tones, with loop start only. The IMS-1000 will recognize ringer frequencies from 16 to 60 Hz
and will operate with all standard analog telephone systems that accept tone dialing.
Certain private telephone systems and public switching equipment may not accept the unit’s dialing
or may generate an unacceptable ring signal. In those cases, a dedicated line may be required for
the unit. Consult the supplier of your telephone system if you encounter problems.

CAUTION: Never install telephone wiring during a lightning storm. Never install telephone

jacks in wet locations unless the jack is specifically designed for wet locations. Never touch
uninsulated telephone wires or terminals unless the telephone line has been disconnected at the
network interface. Use caution when installing or modifying telephone lines.

Sensor Inputs

The sensor inputs are designed to interface with IMS series sensors (See Chapter 5). The use of
RJ-45 jacks for sensor inputs allows the use of existing structured cabling to connect remote sen-
sors.