Ims-4830 water detection sensor, Installation instructions – Sensaphone IMS-1000 Users manual User Manual

Page 76

Advertising
background image

IMS-1000 Manual

76

IMS-4830 Water Detection Sensor

Installation Instructions

Introduction

The IMS-4830 Water Detection Sensor protects your
server and equipment from damaging water leaks from
malfunctioning HVAC systems, cafeteria accidents, or
any general plumbing failures in your facilities. The
IMS-4830 is powered directly by the IMS-1000 unit.
After mounting the sensor, attach the included
WaterRope, and simply lay its orange cable around
your equipment: place it on the floor or beneath a raised
floor; inside a drop-ceiling or in the rafters between
floors; or anywhere you must know about water near
your equipment.
You can attach additional Water Detection sensors to each other to expand your water leak detec-
tion capabilities throughout your facility; alternatively, IMS WaterRopes are designed to plug into
each other to widen your perimeter for any individual sensor.

Package Contents
(1) IMS-4830 Water Detection Sensor
(1) 10' of WaterRope
(5) Adhesive cable clamps
(2) Plastic drywall anchors
(2) #6 Metal tapping screws
(4) Rubber feet

Cabling

The water detection sensor connects to the IMS-1000 via an RJ-45 cable (e.g. CAT5 cable). The
connection from the sensor to the IMS-1000 can utilize your existing network wiring infrastructure.
For example, the sensor may be installed in another room or another floor. Connect the sensor to
your structured wiring network via an RJ-45 jack. At the other end, connect a patch cable from
your structured wiring patch panel directly to the IMS-1000 environment input.

Caution: The IMS sensors are not TCP/IP devices and therefore should not be
connected directly to any wiring infrastructure that is connected to network equipment
such as a hub, router, or switch. Sensors use RJ-45 plugs and cables similar to those
used with Ethernet devices.

Extending the WaterRope

You can extend the monitored area by attaching additional pieces of WaterRope. Simply connect
the new WaterRope to the end of the first. You can have up to ten (10) pieces of WaterRope (100')
connected together from one Water Detection Sensor.

Cascading Water Sensors