Regency Horizon HZ54E-1 Gas Fireplace

INSTALLATION

6) Continue to assemble pipe lengths.

Note: If an offset is necessary in the attic to

avoid obstructions, it is important to
support the vent pipe every 3 feet (0.9
meter), to avoid excessive stress on the
elbows, and possible separation. Wall
straps are available for this purpose

(Diagram

2).


Galvanized pipe is desirable above the roofl ine
due to its higher corrosion resistance. Continue
to add pipe sections through the fl ashing until
the height of the vent cap meets the minimum
height requirements specifi ed in Diagram 5 or
local codes. Note that for steep roof pitches, the
vertical height must be increased.

Diagram 3

Note:
For best results and optimum performance
with each approved venting system, it is highly
recommended to apply “Mill-Pac” sealant to
every inner pipe connection. Failure to do so
may result in drafting or performance issues
not covered under warranty. Silicone (red RTV)
is optional.

UNIT INSTALLATION

WITH VERTICAL

TERMINATION

(Rigid Vent Systems)

Note: A clearance of 2"(51mm) must be

maintained; except when passing
through a wall, ceiling, or at the
termination where the use of a fi restop
or wall thimble reduces the required
clearance to 1-1/2" (38mm). We
recommend framing a 11"(279mm) x
11"(279mm) (inside dimensions) hole
to give structural rigidity for mounting
the termination.

1) Maintain the 1-1/2" (38mm)

clearances (air spaces)
t o c o m b u s t i b l e s w h e n
passing through ceilings,
walls, roofs, enclosures,
attic rafter, or other nearby
combustible surfaces,
ensuring that the use of
a firestop or wall thimble
is used as noted above.
Do not pack air spaces
with insulation. Check
"Venting Arrangement
- Vertical Termination"
section for the maximum
vertical rise of the venting
system and the maximum
h o r i z o n t a l o ff s e t
limitations.

2) Set the gas appliance

in its desired location.
Drop a plumb bob
down from the ceiling
to the position of the
appliance fl ue exit,
and mark the location
where the vent will
penetrate the ceiling.
Drill a small hole at
his point. Next, drop
a plumb bob from
the roof to the hole
previously drilled in the ceiling, and mark the spot
where the vent will penetrate the roof. Determine
if ceiling joists, roof rafters or other framing will
obstruct the venting system. You may wish to
relocate the appliance or to offset, as shown in
Diagram 2 to avoid cutting load bearing members.

3) A Firestop spacer must be installed in the fl oor

or ceiling of every level.

4) Assemble the desired lengths of pipe and elbows.

Ensure that all pipes and elbow connections are
in the fully twist-locked position and sealed.

Diagram 4: The upper half of the fl ashing is

installed under the roofi ng material and not

nailed down until the chimney is installed.

This allows for small adjustments.

5) Cut a hole in the roof centered on the small

drilled hole placed in the roof in Step 2. The hole
should be of suffi cient size to meet the minimum
requirements for clearance to combustibles of
1-1/2"(38mm). Slip the fl ashing under the shingles
(shingles should overlap half the fl ashing) as per
Diagram 4.

Offset Chart

A poor draft, or down drafting can result from high
wind conditions near big trees or adjoining roof
lines, in these cases, increasing the vent height
may solve the problem.

7) Ensure vent is vertical and secure the base of

the fl ashing to the roof with roofi ng rails, slide
storm collar over the pipe section and seal with
a mastic.

8) Install the vertical termination cap by twist-

locking it.

Note: Any closets or storage spaces, which the

vent passes through must be enclosed.

Diagram 5

Roof Pitch

Minimum Vent

Height

Feet

Meters

fl at to 7/12

2

0.61

over 7/12 to 8/12

2

0.61

over 8/12 to 9/12

2

0.61

over 9/12 to 10/12

2.5

0.76

over 10/12 to 11/12

3.25

0.99

over 11/12 to 12/12

4

1.22

over 12/12 to 14/12

5

1.52

over 14/12 to 16/12

6

1.83

over 16/12 to 18/12

7

2.13

over 18/12 to 20/12

7.5

2.29

over 20/12 to 21/12

8

2.44