Catalog Number Explanation

The PowerFlex 400 Adjustable Frequency AC Drive Packages for Fan & Pump
Applications catalog numbering scheme is shown below.

Position

1-3

4

5

6-8

9

10

11

12

13

14

15

16

17

18

19+

23C

D

038

A

1

0

3

N

N

B

A

N

N

-LR

a

b

c

d

e

f

g

h

i

j

k

l

m

n

a

Drive

Code

Type

23C

PowerFlex 400

b

Voltage Rating

Code

Voltage

Ph.

X

208V ac

3

D

480V ac

3

c1

Rating

208V, 60Hz Input

Code

Amps

kW (Hp)

Frame

012

12

2.2 (3.0)

C

017

16.8

3.7 (5.0)

C

024

24

5.5 (7.5)

C

033

30.8

7.5 (10)

C

049

46.2

11 (15)

D

065

64

15 (20)

D

075

75

18.5 (25)

D

090

88

22 (30)

D

120

114

30 (40)

E

145

143

37 (50)

E

Configured drive amp ratings may differ from
stand-alone drive ratings. Configured drives
sized per NEC motor amps.

d

Enclosure

Code

Enclosure

A

NEMA/UL Type 1

H

NEMA/UL Type 12 with Fan and

Filter

X

NEMA/UL Type 3R ‡

E

NEMA/UL Type 4 ‡

‡ Designed for maximum ambient temperature of

40° C with no direct sunlight exposure.

e

HIM

Code

Interface Module

1

Fixed Keypad

f

Emission Class

Code

Rating

0

Not Filtered

j

Package

Code

Description

A

Main Input Disconnect

B

3 Contactor Full Feature Bypass

with Disconnect

M

Main Input Circuit Breaker

N

3 Contactor Full Feature Bypass

with Circuit Breaker

Available with all ratings in NEMA/UL Type 12,
3R, or 4 enclosures (Position d = H, X, or E)
and 160-250 kW (250-350 Hp) ratings in
NEMA/UL Type 1 enclosures (Position d = A).

k

Control

Code

Description

A

Single Motor

l

Code

Rating

N

Reserved

c2

Rating

460V, 60Hz Input

Code

Amps

kW (Hp)

Frame

6P0

4.8

2.2 (3.0)

C

010

7.6

4.0 (5.0)

C

012

11

5.5 (7.5)

C

017

14

7.5 (10)

C

022

21

11 (15)

C

030

27

15 (20)

C

038

34

18.5 (25)

D

045

40

22 (30)

D

060

52

30 (40)

D

072

65

37 (50)

E

088

77

45 (60)

E

105

96

55 (75)

E

142

124

75 (100)

E

170

156

90 (125)

F

208

180

110 (150)

F

260

240

132 (200)

G

310

302

160 (250)

G

370

361

200 (300)

H

460

414

250 (350)

H

Configured amp ratings may differ from stand-
alone drive ratings. Configured drives sized per
NEC motor amps.

g

Version

Code

Version

3

RS485

B

BACnet Adapter

C

ControlNet Adapter

D

DeviceNet Adapter

E

EtherNet/IP Adapter

L

LonWorks Adapter

P

PROFIBUS DP Adapter

h

Code

Rating

N

Reserved

i

Code

Rating

N

Reserved

m

Code

Rating

N

Reserved

n

Options

Code

Description

-LR

3% Input Line Reactor §

-E5

Space Heater - Local Power

§ 3% Input Line Reactor not available for all

package styles. Consult product selection
tables for additional detail.

Available with NEMA/UL Type 3R and 4
enclosures only.

‡ Not available with all ratings at 460V. Consult
product selection tables for details.

Not available with all ratings at 460V. Consult
product selection tables for details.

Advertising