Purge, Bypass running, Operating modes – Rockwell Automation 23C PowerFlex 400 AC Drive Packages for Fan & Pump Apps User Manual

Page 94: Purge bypass running

Advertising
background image

94

Rockwell Automation Publication 23C-IN001B-EN-P - June 2013

Chapter 2

3 Contactor Full Feature Bypass with Disconnect Package (Style B/N)

Purge

A “Purge” input can be wired to terminals 37-38. When this input is closed, the
motor will run at the Purge Frequency, which is defined by Parameter A141
[Purge Frequency], assuming the following conditions exist.

SS1 is either in the DRIVE or BYPASS position.
SS2 is either in the HAND or AUTO position if Jumper P1 on the Bypass

Control Panel (CP1) is in position A.

SS2 is in the HAND, MOTOR OFF or AUTO position if Jumper P1 on

the Bypass Control Panel (CP1) is in Position B.

Interlock wired to terminals 31-32 is closed.
Freeze/Fire Stat wired to terminals 31-33 is closed.

Bypass Running

The “Bypass Running” contact is normally open. When the Bypass Contactor
(BC) is closed the Bypass Running” contact will also be closed.

Operating Modes

Selector Switch 1 (SS1) and Selector Switch 2 (SS2), located on the Bypass
Control Panel (CP1), are used to determine the operating state of the 3
Contactor Full Feature Bypass with Disconnect Package. SS1 is used to select
motor control:
·

DRIVE = Drive keypad/terminal block controls the motor

·

DRIVE TEST = Drive is powered but is not controlling the motor

·

BYPASS = Motor runs across 3-Phase line

Jumper P2 on the Bypass Control Panel (CP1) allows the drive to be powered
while running in bypass. This is accomplished by moving Jumper P2 to position
B-C and turning SS1 from BYPASS to DRIVE TEST. If Jumper P2 is in position
A-B, the drive cannot be powered while running in bypass. SS2 selects the source
of the Start, Stop, and Drive Speed Reference as defined in

Table 10

.

Table 10 - Command and Reference Selection

ATTENTION: A Purge command will take precedence over a Stop command from
the Comm Port/Network. Insure that another stop method is available if
stopping is necessary during a purge.

SS1

(1)

Selection

(1) See

Figure 67

on page

89

for details on selector switch location.

SS2

(1)

Selection Start Command

(2)

(2) When “Auto” is selected, the Start Command is defined by P036 [Start Source]. Factory default is configured for terminal block

control. Refer to the PowerFlex 400 User Manual for other control schemes.

Stop Command

Drive Speed Reference

(3)

(3) When “Auto” is selected, the Speed Reference is defined by P038 [Speed Reference]. Analog In1 has control by factory default. Refer

to the PowerFlex 400 User Manual for other control schemes.

TB

Keypad

None

TB

Keypad

None

TB

Keypad

None

DRIVE

HAND
MOTOR OFF
AUTO

DRIVE TEST

HAND
MOTOR OFF
AUTO

BYPASS

HAND

Automatically Starts

Automatically Starts

Motor Runs at Base Speed

MOTOR OFF
AUTO

Motor Runs at Base Speed