Watts Loss

The following table lists watt loss data for PowerFlex Drive Packages for Fan and
Pump Applications running at full load, full speed and a factory default PWM
frequency of 4kHz.

Table 11 - Watts Loss at Full Load/Speed, 4 kHz

Voltage

kW

Hp

Total Watts

208V AC

2.2

3.0

180

3.7

5.0

220

5.5

7.5

308

7.5

10

375

11

15

498

15

20

660

18.5

25

744

22

30

788

30

40

1065

37

50

1210

460V AC

2.2

3.0

135

3.7

5.0

195

5.5

7.5

209

7.5

10

253

11

15

336

15

20

443

18.5

25

499

22

30

529

30

40

713

37

50

810

45

60

1132

55

75

1288

75

100

1560

90

125

1910

110

150

2310

132

200

3711

160

250

4208

200

300

4916

250

350

6167

Advertising