Installing the Required External/Separate Input Disconnect

An input disconnect must be installed in the line before the drive input terminals
in accordance with local, national, and international codes, such as NEC/CEC. If
an input disconnect is not installed as a factory option, the disconnect should be
sized according to the in-rush current as well as any additional loads the
disconnect might supply. The trip rating for the in-rush current (10 to 12 times
full load current) should be coordinated with that of the input isolation
transformer, if used.

Installing Input/Output Power Wiring

Table 16 - Style A Terminals

Table 17 - Style B Terminals

208V AC Hp

480V AC Hp

Maximum Tightening Torque

Input Power
3…5

3…10

12 lb•in

7.5…10

15…25

35 lb•in

15…20

30…50

35 lb•in

25…50

60…350

275 lb•in

Output Power
3…10

3…20

26 lb•in

15…30

25…40

45 lb•in

50…60

49.5 lb•in

40…50

75…150

173 lb•in

200…250

260 lb•in

300…350

354 lb•in

208V AC Hp

480V AC Hp

Maximum Tightening Torque

Input Power
3…5

3…10

12 lb•in

7.5…10

15…25

35 lb•in

15…20

30…50

35 lb•in

25…50

60…350

275 lb•in

Output Power
3…7.5

3…7.5

13 lb•in

10…20

10…30

19 lb•in

25…30

40…75

40 lb•in

100…150

275 lb•in

40…50

200…300

500 lb•in

350

375 lb•in