Chapter 4 - electrical installation, Power wire size requirements, Power terminal block specification – Rockwell Automation 23C PowerFlex 400 AC Drive Packages for Fan & Pump Apps User Manual

Page 183: Chapter 4, Electrical installation, Chapter

Advertising
background image

Rockwell Automation Publication 23C-IN001B-EN-P - June 2013

183

Chapter

4

Electrical Installation

This chapter provides information on electrical installation of a PowerFlex Drive
Package for Fan and Pump Applications.

Power Wire Size
Requirements

Wire size should be determined based on the size of the conduit openings, and
applicable local, national and international codes such as NEC/CEC.

Power Terminal Block
Specification

Input power wiring should be sized according to applicable codes to handle the
drive's continuous-rated input current. Output wiring should be sized according
to applicable codes to the handle the drive's continuous-rated output current. See

Table 14

for the range of power wire sizes that the terminals can accommodate.

Table 14 - Power Wire Sizes

Topic

Page

Power Wire Size Requirements

183

Power Terminal Block Specification

183

Control and Signal Wiring

184

Installing Input Power Wiring

184

Installing Output Power Wiring

185

Installing an Optional Transformer or Reactor

185

ATTENTION: National codes and standards (NEC, VDE, BSI, etc.) and local codes
outline provisions for safely installing electrical equipment. Installation must
comply with specifications regarding wire types, conductor sizes, branch circuit
protection, and disconnect devices. Failure to do so may result in personal injury
and/or equipment damage.

Name

Package
Style

Hp

Wire Size Range

Torque

208V AC

480V AC

Minimum

Maximum

Input Power
L1(R), L2 (S), L3 (T)

A & B

3…5

3…10

14 AWG

8 AWG

12

7.5…10

15…25

14 AWG

4 AWG

35

15…20

30…50

14 AWG

2 AWG

35

25…40

60…100

6 AWG

250 MCM

275

50

125…200

(2) 1/0

350 MCM

275

250…300

(2) 2/0

350 MCM

275

350

(3) 3/0

350 MCM

275