Control transformer (t1), Bypass control interface (cp1) – Rockwell Automation 23C PowerFlex 400 AC Drive Packages for Fan & Pump Apps User Manual

Page 89

Advertising
background image

Rockwell Automation Publication 23C-IN001B-EN-P - June 2013

89

3 Contactor Full Feature Bypass with Disconnect Package (Style B/N)

Chapter 2

Control Transformer (T1)

115V AC control power is obtained via a supplied control power transformer.
The control transformer is fused on the primary.

Bypass Control Interface (CP1)

The operator interface on the bypass option box shows the following LEDs:

Ready (green) - On when power is applied to the drive-bypass unit.
Interlock Open (amber) - On when the customer interlock or Aux Fault is

de-energized.

Bypass Run (green) - On when the bypass contactor (BC) is energized.
Bypass Trip (red) - On when a bypass fault condition exists (for example,

bypass motor overload has tripped).

Purge (amber) - On when the purge condition is active.
Drive Output Enable (Green) - On when the drive output contactor

(DOC) is energized.

In addition, the Bypass Control Interface contains two selector switches. Selector
Switch 1 (SS1) determines the state of the DIC, DOC and BC contactors.
Selector Switch 2 (SS2) determines the source of control logic.

Figure 67 - Bypass Control Interface

MOTOR

OFF

DRIVE

TEST

HAND

AUTO

DRIVE

BYPASS

MOTOR

BYPASS

RUN

BYPASS

TRIP

PURGE

DOC

DRIVE

OUTPUT

ENABLE

DIC

INTERLOCK

OPEN

BC

OL

FOR DRIVE STATUS

SEE DRIVE DISPLAY

DRIVE

READY

SS2

SS1