3 Contactor Full Feature Bypass with Disconnect Package (Style B/N)

Chapter 2

Parameter Defaults

(Style B/N)

Parameter Name

Number

Default

Output Freq

b001

Read Only

Commanded Freq

b002

Read Only

Output Current

b003

Read Only

Output Voltage

b004

Read Only

DC Bus Voltage

b005

Read Only

Drive Status

b006

Read Only

Fault 1 Code

b007

Read Only

Process Display

b008

Read Only

Output Power

b010

Read Only

Elapsed MWh

b011

Read Only

Elapsed Run Time

b012

Read Only

Torque Current

b013

Read Only

Drive Temp

b014

Read Only

Elapsed kWh

b015

Read Only

Motor NP Volts

P031

Drive Rated Volts

Motor NP Hertz

P032

60 Hz

Motor OL Current

P033

Drive Rated Amps

Minimum Freq

P034

0.0 Hz

Maximum Freq

P035

60 Hz

Start Source

P036

6 “2-W Lvl/Enbl”

(1)

Stop Mode

P037

1 “Coast, CF”

Speed Reference

P038

2 “Analog In1”

Accel Time 1

P039

20.00 Secs

Decel Time 1

P040

20.00 Secs

Reset To Defalts

P041

0 “Ready/Idle”

Auto Mode

P042

0 “No Function”

(1)

Digital In1 Sel

T051

1 “Purge”

Digital In2 Sel

T052

3 “Local”

Digital In3 Sel

T053

10 “Clear Fault”

Digital In4 Sel

T054

4 “Comm Port”

Relay Out1 Sel

T055

0 “Ready/Fault”

Relay Out1 Level

T056

0.0

Relay 1 On Time

T058

0.0 Secs

Relay 1 Off Time

T059

0.0 Secs

Relay Out2 Sel

T060

2 “MotorRunning”

Relay Out2 Level

T061

0.0

Relay 2 On Time

T063

0.0 Secs

Relay 2 Off Time

T064

0.0 Secs

Opto Out Sel

T065

1 “At Frequency”

Opto Out Level

T066

0.0

Opto Out Logic

T068

0 “Normally Open”

Analog In 1 Sel

T069

2 “0-10V”

Analog In 1 Lo

T070

0.0%

Analog In 1 Hi

T071

100.0%

Analog In 1 Loss

T072

0 “Disabled”

Analog In 2 Sel

T073

1 “4-20 mA

(1)

Analog In 2 Lo

T074

0.0%

Analog In 2 Hi

T075

100.0%

Analog In 2 Loss

T076

0 “Disabled”

Sleep-Wake Sel

T077

0 “Disabled”

Sleep Level

T078

10.0%

Sleep Time

T079

0.0 Secs

Wake Level

T080

15.0%

Wake Time

T081

0.0 Secs

Analog Out1 Sel

T082

0 “OutFreq 0-10”

Analog Out1 High

T083

100%

Analog Out1 Setpt

T084

0.0%

Analog Out2 Sel

T085

1 “OutCurr 0-10”

Analog Out2 High

T086

100%

Analog Out2 Setpt

T087

0.0%

Language

C101

1 “English”

Comm Format

C102

0 “RTU 8-N-1”

Comm Data Rate

C103

3 “9600”

Comm Node Addr

C104

100

Comm Loss Action

C105

0 “Fault”

Comm Loss Time

C106

5.0 Secs

Comm Write Mode

C107

0 “Save”

Purge Frequency

A141

5.0 Hz

Internal Freq

A142

60.00 Hz

Preset Freq 0

A143

0.0 Hz

Preset Freq 1

A144

5.0 Hz

Preset Freq 2

A145

10.0 Hz

Preset Freq 3

A146

20.0 Hz

Accel Time 2

A147

30.00 Secs

Decel Time 2

A148

30.00 Secs

S Curve %

A149

20%

PID Trim Hi

A150

60.0 Hz

PID Trim Lo

A151

0.0 Hz

PID Ref Sel

A152

0 “PID Disabled”

PID Feedback Sel

A153

0 “Analog In 1”

PID Prop Gain

A154

0.01

PID Integ Time

A155

2.0 Secs

PID Diff Rate

A156

0.00

PID Setpoint

A157

0.0%

PID Deadband

A158

0.0%

PID Preload

A159

0.0 Hz

Process Factor

A160

30.0

Auto Rstrt Tries

A163

0

Auto Rstrt Delay

A164

1.0 Secs

Start At PowerUp

A165

1 “Enabled”

(1)

Reverse Disable

A166

1 “Rev Disabled”

Flying Start En

A167

1 “Enabled”

(1)

PWM Frequency

A168

4.0 kHz

PWM Mode

A169

1 “2-Phase”

Boost Select

A170

4 “45.0, VT”

Start Boost

A171

2.5%

Break Voltage

A172

25.0%

Break Frequency

A173

15.0 Hz

Maximum Voltage

A174

Drive Rated Volts

Slip Hertz @ FLA

A175

2.0 Hz

DC Brake Time

A176

0.0 Secs

DC Brake Level

A177

Drive Rated Amps

DC Brk Time@Strt

A178

0 (Disabled)

Current Limit 1

A179

Drive Rated Amps

Current Limit 2

A180

Drive Rated Amps

Motor OL Select

A181

0 “No Derate”

Drive OL Mode

A182

3 “Both-PWM 1st”

SW Current Trip

A183

0.0 (Disabled)

Load Loss Level

A184

0.0 (Disabled)

Load Loss Time

A185

0 Secs

Stall Fault Time

A186

0 “60 Seconds”

Bus Reg Mode

A187

1 “Enabled”

Skip Frequency 1

A188

0 Hz

Skip Freq Band 1

A189

0.0 Hz

Skip Frequency 2

A190

0 Hz

Skip Freq Band 2

A191

0.0 Hz

Skip Frequency 3

A192

0 Hz

Skip Freq Band 3

A193

0.0 Hz

Compensation

A194

1 “Electrical”

Reset Meters

A195

0 “Ready/Idle”

Testpoint Sel

A196

400

Fault Clear

A197

0 “Ready/Idle”

Program Lock

A198

0 “Unlocked”

Motor NP Poles

A199

4

Relay Out3 Sel

R221

0 “Ready/Fault”

Relay Out3 Level

R222

0.0

Relay Out4 Sel

R224

0 “Ready/Fault”

Relay Out4 Level

R225

0.0

Relay Out5 Sel

R227

0 “Ready/Fault”

Relay Out5 Level

R228

0.0

Relay Out6 Sel

R230

0 “Ready/Fault”

Relay Out6 Level

R231

0.0

Relay Out7 Sel

R233

0 “Ready/Fault”

Relay Out7 Level

R234

0.0

Relay Out8 Sel

R236

0 “Ready/Fault”

Parameter Name

Number

Default

Relay Out8 Level

R237

0.0

Aux Motor Mode

R239

0 “Disabled”

Aux Motor Qty

R240

1 “1 Aux Mtr”

Aux 1 Start Freq

R241

50.0 Hz

Aux 1 Stop Freq

R242

25.0 Hz

Aux 1 Ref Add

R243

0.0%

Aux 2 Start Freq

R244

50.0 Hz

Aux 2 Stop Freq

R245

25.0 Hz

Aux 2 Ref Add

R246

0.0%

Aux 3 Start Freq

R247

50.0 Hz

Aux 3 Stop Freq

R248

25.0 Hz

Aux 3 Ref Add

R249

0.0%

Aux Start Delay

R250

5.0 Secs

Aux Stop Delay

R251

3.0 Secs

Aux Prog Delay

R252

0.50 Secs

Aux AutoSwap Tme

R253

0.0 Hr

Aux AutoSwap Lvl

R254

50.0%

Control Source

d301

Read Only

Contrl In Status

d302

Read Only

Comm Status

d303

Read Only

PID Setpnt Displ

d304

Read Only

Analog In 1

d305

Read Only

Analog In 2

d306

Read Only

Fault 1 Code

d307

Read Only

Fault 2 Code

d308

Read Only

Fault 3 Code

d309

Read Only

Fault 1 Time-hr

d310

Read Only

Fault 1 Time-min

d311

Read Only

Fault 2 Time-hr

d312

Read Only

Fault 2 Time-min

d313

Read Only

Fault 3 Time-hr

d314

Read Only

Fault 3 Time-min

d315

Read Only

Elapsed Time-hr

d316

Read Only

Elapsed Time-min

d317

Read Only

Output Powr Fctr

d318

Read Only

Testpoint Data

d319

Read Only

Control SW Ver

d320

Read Only

Drive Type

d321

Read Only

Output Speed

d322

Read Only

Output RPM

d323

Read Only

Fault Frequency

d324

Read Only

Fault Current

d325

Read Only

Fault Bus Volts

d326

Read Only

Status @ Fault

d327

Read Only

(1)

The default values of these parameters differ from Factory
Defaults. Setting P041 [Reset To Defalts] to 1 “Factory Rset” will
change these parameter settings to the defaults listed in the
PowerFlex 400 User Manual.

Parameter Name

Number

Default

ATTENTION: Parameter
A165 [Start At PowerUp] ships
from the factory enabled. This
feature allows a Run
command to automatically
cause the drive to resume
running at commanded speed
after drive input power is
restored. Equipment damage
and/or personal injury may
result if this parameter is used
in an inappropriate
application. Do not use this
function without considering
applicable local, national and
international codes, standards,
regulations or industry
guidelines.