Bryant 524J User Manual

Page 11

Advertising
background image

11

Unit Isolation -- Where extremely quiet operation is

essential, install isolators between floor and base of unit,

or between ceiling and top section of unit.

Be sure that unit is level and adequately supported. Use

channels at front and sides of unit for reference points

when leveling.

Refrigerant Piping Access -- The 524J Series units come

with standard knockouts for refrigerant piping. These

knockouts are located on both sides of the unit for

installation flexibility. The standard knockouts provide

sufficient access to the unit’s coils for all 524J*25A, 28A

and 30A units. The 524J*25H requires additional holes

which must be field--fabricated to accommodate the

piping. See Fig. 8 for positions and dimensions for the

additional access holes required. Recommended access

hole use is also listed for all units. Note that Fig. 8 shows

the access holes on the control--box side of the unit; this is

the side of the unit with the coil headers, so it is used most

often for piping access.
IMPORTANT:

Do

not

bury

refrigerant

piping

underground.
Refrigerant Piping -- See Tables 1A–1D for refrigerant

pipe connection sizes. For ease in brazing, it is

recommended that all internal solder joints be made

before unit is placed in final position.

The

524J

direct--expansion

units

have

internal

factory--installed thermostatic expansion valves (TXVs),

distributors, and nozzles for use with R--410A. See Table 2

for part numbers. Knockouts are provided in the unit corner

posts for 524J refrigerant piping. See Fig. 8, which also lists

recommended knockouts and access holes to use for each

524J unit size. Recommended fittings are listed in Table 3.

The sensor bulb capillary tubes must be routed from the

TXVs inside the unit through one of the piping access

holes. Clamp the TXV sensor bulb on a vertical portion of

the suction line, outside the unit. See Fig. 9.
NOTE: Be sure to remove the styrofoam shipping pad
from the TXV. Verify that it has been removed. See Fig. 5.
IMPORTANT: Never attach the sensor to the suction
manifold. Do NOT mount the sensor on a trapped portion
of the suction line.
The 524J Series evaporator coils have a face--split design.

Ensure that lower circuit of coil is first on/last off when

connected to the condensing unit and/or system controls.

See Fig. 10.

External TXV equalizer connections are provided and

factory--brazed into the coil suction manifolds.

If suction line must be horizontal, clamp bulb to suction

line at least 45 degrees above bottom, at approximately

the 4 o’clock or 8 o’clock position. See Fig.11.

4

3
2

1

7
6
5

A

B

C

C10838

UNIT

USE HOLE

NUMBERS

FIELD--FABRICATED HOLE DIAMATERS

in. (mm)

FIELD--FABRICATED HOLE POSITION DIMENSIONS

in. (mm)

No. 5

No. 6

No. 7

A

B

C

524J*25A, 28A, 30A

1,2, 3, 4

524J*25H

3*, 5, 6, 7

1

1

/

8

(28.6)

1

1

/

8

(28.6)

1

3

/

4

(44.5)

3.25 (82.6)

6.125 (155.6)

10.38 (263.7)

*Must be enlarged from 1

1

/

8

in. (28.6mm) to 1

3

/

4

in. (44.5mm)

NOTE: Access hole knockouts 1--- 4 are factory--- supplied.

Fig. 8 -- Refrigerant Piping Access Holes

524J

Advertising