Caution – Bryant 524J User Manual

Page 17

Advertising
background image

17

C10695

Fig. 17 -- Unit Wiring

Table 6 – Fan Contactor Coil Data

UNIT

524J*

VOLTAGE

(vac)

MAXIMUM

HOLDING VA

25A, 25H, 28A, 30A

24

10

Connecting Ductwork -- Refer to the System Design

Manual for the recommended design and layout of

ductwork. Fig. 18 shows recommended duct connection to

units with 2 fans.

UNIT OPERATION HAZARD

Failure to follow this caution could cause equipment

damage.

Do not operate unit without ductwork or discharge

plenum unless fan speed has been adjusted for

external static pressure of zero in. wg. Failure to do so

may result in motor overload.

CAUTION

!

DISCHARGE CONNECTIONS — Duct flanges are

factory--supplied; they are shipped inside the unit attached

to the hairpin end of the coil tube sheet for field

installation. Using the existing screws, install the duct

flanges on the unit’s fan deck. Each fan discharge requires

2 flanges; each flange must be bent in the middle to

conform to the discharge opening. See Fig. 19. After

flanges are installed, connect them to the supply duct

using a canvas connection to prevent vibration. It is

important that this connection be properly fabricated to

prevent high air friction losses and air noise.

RETURN CONNECTIONS — When using return--air

ductwork, route return--air duct to the unit’s return air inlet

near the filter rack, using a canvas connection to prevent

transmission of unit vibration. If the duct blocks off the

unit’s access panel, provide a slip joint in the ductwork to

permit removal for servicing.

OUTDOOR--AIR INLET CONNECTIONS — Connect

outdoor--air inlet to field--installed accessory economizer.

Refer to Economizer Installation Instructions.

Return--Air Filters -- Type and size of filters are shown

in Tables 1A – 1D and are factory--supplied and

factory--installed. In all units with 2 fans, a filter

replacement tool (hook) is shipped inside the unit for field

use when replacing filters. See the Service section for

instructions on filter element replacement.

524J