Bryant 524J User Manual

Page 32

Advertising
background image

32

Legend and Notes for Tables 10A and 10C

LEGEND

Bhp --- Brake Horsepower Input to Fan

ESP --- External Static Pressure
NOTES:
1. Maximum allowable fan speed for size 25 units is 1200 rpm . Maximum

allowable fan speed for size 28 and 30 units is 1100 rpm.

2. Fan performance is based on deductions for wet coil, clean 2-in. filters,

and unit casing. See table at right for factory-supplied filter pressure drop.

3. Refer to fan motor and drive tables for additional data.

FACTORY-SUPPLIED PRESSURE DROP — ENGLISH

UNIT

AIRFLOW

(Cfm)

PRESSURE DROP

(in. wg)

524J*25A

524J*25H

6,000

0.12

8,000

0.19

10,000

0.26

524J*28A

7,500

0.15

10,000

0.22

12,500

0.30

524J*30A

9,000

0.19

12,000

0.29

15,000

0.40

Legend and Notes for Tables 10B and 10D

LEGEND

ESP --- External Static Pressure

NOTES:
1. Maximum allowable fan speed for size 25 units is 20 r/s. Maximum

allowable fan speed for size 28 and 30 units is 18.3 r/s.

2. Fan performance is based on deductions for wet coil, clean 51---mm

filters, and unit casing. See table at right for factory-supplied filter

pressure drop.

3. Refer to fan motor and drive tables for additional data.

FACTORY-SUPPLIED PRESSURE DROP — SI

UNIT

AIRFLOW

(L/s)

PRESSURE DROP

(Pa)

524J*25A

524J*25H

2900

32

3800

47

4700

64

524J*28A

3500

36

4700

55

5900

76

524J*30A

4250

47

5650

71

7050

98

524J

Advertising