Coil Removal -- Remove unit panels and corner posts as

required. Disconnect coil connections and remove fastening

screws. Remove coil through end or side sections of unit.

Cleaning Cooling Coil -- Remove return--air filters.

Remove any heavy dirt that may have accumulated on

underside of coil. Coil can be cleaned more easily with a

stiff brush, vacuum cleaner, or compressed air when coil

is dry. If coil is wet or if water is to be used for cleaning,

guard against splashing water on electrical components or

damaging surrounding area. Clean coil baffles as

applicable and check for tight fit to be sure air does not

bypass coil.

Cleaning Insulation -- The insulation contains an

immobilized antimicrobial agent that helps prevent the

growth of bacteria and fungi. Clean the inner surface of

the insulation according to the separate maintenance

instructions shipped with the unit.

Replacing Filters -- Filters can be removed and installed

from either side of the unit. Install new filters in units that

have one fan as follows:

1. Remove the side access panel (retain screws).
2. Remove the filter retainer clip (see Fig. 27).
3. Remove old filters by lifting and tilting them out of

the filter track. See Fig. 15 and 28. Use the factory--

supplied filter hook to slide filters within reach for re-

moval. The filter hook is shipped inside the unit in

the filter track

4. Reverse the procedure to install new filters.

UNIT OPERATION HAZARD
Failure to follow this caution could cause equipment

damage.
Do not operate unit without air filters.

CAUTION

!

SLIDE

FILTER
RETAINER
CLIP

C10703

Fig. 27 -- Remove Filter Retainer Clip

C10704

Fig. 28 -- Filter Removal/Replacement