Bryant 524J User Manual

Page 5

Advertising
background image

5

Table 1C — 524J*25H Physical Data, English — Heat Pump Units

UNIT 524J*

25H

NOMINAL CAPACITY (Tons)

20

OPERATING WEIGHT (lb)

Base Unit with TXV

720

Plenum

140

FANS

Qty...Diam. (in.)

2...15

Nominal Airflow (cfm)

8000

Airflow Range (cfm)

6000---10000

Nominal Motor Hp (Standard Motor)

208/230---3---60 and 460---3---60

5.0

575---3---60

5.0

Motor Speed (rpm)

208/230---3---60 and 460---3---60

1745

575---3---60

1745

REFRIGERANT

R---410A

Operating charge (lb)

(approx per circuit)*

3.5/3.5

DIRECT---EXPANSION COIL

Enhanced Copper Tubes, Aluminum Sine---Wave Fins

Max Working Pressure (psig)

650

Face Area (sq ft)

19.9

No. of Splits

2

No. of Circuits per Split

2

Split Type...Percentage

Face....50/50

Rows...Fins/in.

4...15

PIPING CONNECTIONS,

Quantity...Size (in.)

DX Coil — Suction (ODF)

2...1

1/8

DX Coil — Liquid Refrigerant (ODF)

2...

5/8

Steam Coil, In (MPT)

1...2

1/2

Steam Coil, Out (MPT)

1...1

1/2

Hot Water Coil, In (MPT)

1...2

Hot Water Coil, Out (MPT)

1...2

Condensate (PVC)

1...1

1/4

ODM/1 IDF

FILTERS

Throwaway — Factory Supplied

Quantity...Size (in.)

4...16 x 20 x 2

4...16 x 24 x 2

Access Location

Right or Left Side

STEAM COIL**

Max Working Pressure (psig at 260° F)

20

Total Face Area (sq ft)

13.33

Rows...Fins/in.

1...10

HOT WATER COIL**

Max Working Pressure (psig)

150

Total Face Area (sq ft)

13.33

Rows...Fins/in.

2...8.5

Water Volume

(gal)

13.9

(ft

3

)

1.85

LEGEND

DX — Direct Expansion

TXV — Thermostatic Expansion Valve

*

Units are shipped without refrigerant charge.

**

Field installed accessory only.

524J

Advertising