Bryant 524J User Manual

Page 20

Advertising
background image

20

Fan Motor Lubrication -- Fan motor supplied with unit is

permanently

lubricated

and

requires

no

further

lubrication.

Fan Shaft Bearings -- Size 25--30 units have pillow--block

bearings (Fig. 22) that must be lubricated with suitable

bearing grease approximately every 3 months. See Table 7

for suitable lubricants.

Table 7 – Lubricant Data

MANUFACTURER

LUBRICANT

Mobil

Mobilplex EP No. 2

Sunoco

Prestige 42

Texaco

Multifak 2

Texaco

Regal AFB---2*

*Preferred lubricant, contains rust and oxidation inhibitors.

C10698

Fig. 22 -- Fan Shaft, Bearings, and Fan Wheel (Typical)

Centering Fan Wheel -- If fan and fan shaft assembly are

not properly centered, blades may scrape against the

blower side scroll plate or may create an objectionable

whistling noise. It may be necessary to adjust individual

fan wheels or move entire fan shaft. See the following two

sections.

Fan Shaft Position Adjustment -- Loosen setscrew or

locking collar of each fan shaft bearing. Slide shaft into

correct position and replace locking collar (Fig. 23). To

replace locking collar, push collar up against inner face of

bearing. Turn collar in direction of fan rotation until tight,

and tighten setscrew. Tightening locking collar in

direction of fan rotation results in further tightening of

collar should setscrew work itself loose.

C10699

Fig. 23 -- Fan Shaft Bearing

C10700

Fig. 24 -- Fan Motor Mounting

524J