Bryant 524J User Manual

Page 16

Advertising
background image

16

Table 4 – Electrical Data, Standard Motors

UNIT

V---PH---Hz

{

VOLTAGE

LIMITS

FAN MOTOR

POWER SUPPLY

Hp (kW)

FLA

Minimum

Circuit Amps

MOCP

524J*25A

524J*25H

208/230---3---60

187---253

5.0 (3.73)

14.7/13.6

18.4/17.0

30/25

460---3---60

414---506

5.0 (3.73)

6.8

8.5

15

575---3---60

518---632

5.0 (3.73)

5.1

6.4

15

524J*28A

208/230---3---60

187---253

7.5 (5.59)

21.4/19.4

26.9/24.3

45/40

460---3---60

414---506

7.5 (5.59)

9.7

12.1

20

575---3---60

518---632

7.5 (5.59)

7.8

9.8

15

524J*30A

208/230---3---60

187---253

10.0 (7.46)

28.0/25.2

35.0/31.5

60/50

460---3---60

414---506

10.0 (7.46)

12.6

15.8

25

575---3---60

518---632

10.0 (7.46)

10.3

12.9

20

See Legend and Notes below.

Table 5 – Electrical Data, Alternate Motors

UNIT

V---PH---Hz*

VOLTAGE

LIMITS

FAN MOTOR

POWER SUPPLY

Hp (kW)

FLA

Minimum

Circuit Amps

MOCP

524J*25A

524J*25H

208/230---3---60

187---253

7.5 (5.59)

21.4/19.4

26.9/24.3

45/40

460---3---60

414---506

7.5 (5.59)

9.7

12.1

20

575---3---60

518---632

7.5 (5.59)

7.8

9.8

15

524J*28A

524J*30A

208/230---3---60

187---253

10.0 (7.46)

28.0/25.2

35.0/31.5

60/50

460---3---60

414---506

10.0 (7.46)

12.6

15.8

25

575---3---60

518---632

10.0 (7.46)

10.3

12.9

20

See Legend and Notes below.

Legend and Notes for Tables 4 and 5

LEGEND:
FLA

--- Full Load Amps

MOCP --- Maximum Overcurrent Protection
{

Motors are designed for satisfactory operation within 10% of

normal voltage shown. Voltages should not exceed the limits

shown in the Voltage Limits column.

NOTES:

1. Minimum circuit amps (MCA) and MOCP values are calcu-

lated in accordance with The NEC. Article 440.

2. Motor FLA values are established in accordance with Under-

writers’ Laboratories (UL). Standard 1995.

3.

Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply

voltage is greater than 2%. Use the formula in the example

(see column to the right) to determine the percentage of volt-

age imbalance.

4. Installation with Accessory Electric Heaters

Size the Field Power Wiring between the heater TB1 and the

524J indoor fan motor per NEC Article 430---28 (1) or (2)

(depends on length of conduit between heater enclosure and

524J power entry location). Install wires in field---installed

conduit.

Example: Supply voltage is 230-3-60

% Voltage Imbalance

= 100 x

max voltage deviation from average voltage

average voltage

AB = 393 v
BC = 403 v
AC = 396 v

Average Voltage =

(393 + 403 + 396)

=

1192

3

3

=

397

Determine maximum deviation from average voltage.
(AB) 397 – 393 = 4 v
(BC) 403 – 397 = 6 v
(AC) 397 – 396 = 1 v
Maximum deviation is 4 v.
Determine percent of voltage imbalance.

% Voltage Imbalance

= 100 x

6

397

= 1.5%

This amount of phase imbalance is satisfactory as it is below the

maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than

2%, contact your local electric utility company immediately.