Bryant 524J User Manual

Page 6

Advertising
background image

6

Table 1D — 524J*25H Physical Data, SI — Heat Pump Units

UNIT 524J*

25H

NOMINAL CAPACITY (kW)

70

OPERATING WEIGHT (kg)

Base Unit with TXV

326

Plenum

44

FANS

Qty...Diam. (mm)

2...381

Nominal Airflow (L/s)

3775

Airflow Range (L/s)

2831---4719

Nominal Motor kW (Standard Motor)

208/230---3---60 and 460---3---60

3.73

575---3---60

3.73

Motor Speed (r/s)

208/230---3---60 and 460---3---60

29.1

575---3---60

29.1

REFRIGERANT

R---410A

Operating charge (kg)

(approx per circuit)*

1.59/1.59

DIRECT---EXPANSION COIL

Enhanced Copper Tubes, Aluminum Sine---Wave Fins

Max Working Pressure (kPag)

4482

Face Area (sq m)

1.85

No. of Splits

2

No. of Circuits per Split

2

Split Type...Percentage

Face...50/50

Fins/m

591

PIPING CONNECTIONS,

Quantity...Size (in.)

DX Coil — Suction (ODF)

2...1

1/8

DX Coil — Liquid Refrigerant (ODF)

2...

5/8

Steam Coil, In (MPT)

1...2

1/2

Steam Coil, Out (MPT)

1...1

1/2

Hot Water Coil, In (MPT)

1...2

Hot Water Coil, Out (MPT)

1...2

Condensate (PVC)

1...1

1/4

ODM/1 IDF

FILTERS

Throwaway — Factory Supplied

Quantity...Size (mm)

4...406 x 610 x 51

4...406 x 508 x 51

Access Location

Right or Left Side

STEAM COIL**

Max Working Pressure (kPag at 126° C)

138

Total Face Area (sq m)

1.24

Rows...Fins/m

1...394

HOT WATER COIL**

Max Working Pressure (kPag)

1034

Total Face Area (sq m)

1.24

Rows...Fins/m

2...335

Water Volume

(L)

52.6

(m

3

)

0.052

LEGEND

DX — Direct Expansion
TXV — Thermostatic Expansion Valve

*

Units are shipped without refrigerant charge.

**

Field installed accessory only.

524J

Advertising