Warning, Important! / important, Start--up – Bryant 524J User Manual

Page 19: Service, Installer / installateur

Advertising
background image

19

START--UP

Before starting unit, check the following and correct as

necessary:

S

Is unit solidly supported?

S

Is fan adjusted for speed and pulley alignment?

S

Are pulleys, motor, and bearings securely mounted?

S

Are there any loose parts that will rattle or vibrate?

S

Is condensate drain pan pitched for correct drainage?

S

Are coil baffle plates tight against coil to prevent air
bypass?

S

Are all panels securely fastened?

S

Are all electrical connections correct and tight?

S

Is TXV bulb located on suction tube per Fig. 20?

S

Is the capillary tube to the bulb free of kinks and not
subject to pinching?

S

Is the bulb well secured to the suction tube with strap?

Also refer to condensing unit or outdoor heat pump section

instructions before starting a split system. A split system

start--up checklist is provided at the end of these instructions.

IMPORTANT! / IMPORTANT

40RU500072 2.0

The sensor bulb capillary tubes must be routed from the TXVs inside the unit through one of the piping

access holes. Clamp the TXV sensor bulb on a vertical portion of the suction line, outside the unit.
See Fig. 7 in the installation, start-up and service instruction. Super heat must be adjusted in field.

Les tubes capillaires du capteur doivent être acheminé à partir du détendeur thermostatique situé à l'intérieur

de l'appareil au travers de l'un des trous d'accès de conduites. Attacher le capteur sur une portion verticale

de la conduite de succion, à l'extérieur de l'appareil. Voir la Figure 7 dans le manuel d'installation, de mise

en marche, et d'entretien. La surchauffe doit être ajustée sur place.

AIR FLOW
CIRCULATION
D'AIR

UPPER SPLIT
BLOC SUPÉRIEUR

LOWER
SPLIT
BLOC
INFÉRIEUR

AIR FLOW
CIRCULATION

D'AIR

15 DIAMS MIN

15 x DIA. MIN

10 DIAMS

10 x DIA. MIN

TXV SENSING
BULB
CAPTEUR TXV

15 DIAMS MIN

15 x DIA. MIN

10 DIAMS

10 x DIA. MIN

TXV
SENSING
BULB
CAPTEUR TXV

EQUALIZER LINE
CONDUITE D'ÉQUILIBRAGE

SIGHT GLASS
HUBLOT

8 DIAMS MIN
8 x DIA. MIN

TXV

SOLENOID
VALVE
VANNE
SOLÉNOÏDE

FILTER

DRIER

FILTRE

DESSICCATEUR

TXV

EQUALIZER LINE

CONDUITE D'ÉQUILIBRAGE

8 DIAMS MIN

8 x DIA. MIN

INDOOR COIL
ÉCHANGEUR INTÉRIEUR

C10827

Fig. 20 -- Label, TXV Bulb Location

Adjusting TXV for Superheat —

The unit--mounted thermostatic expansion valve(s) is/are

factory set to provided superheat at the bulb location in

10_F to 15_F (5.5_C to 8.3_C) range. Actual system load

conditions may require adjustment of the factory setting.

To adjust the TXV superheat setting:

1. Remove the seal cap from the bottom of the TXV

body.

2. To increase superheat, turn the stem clockwise. To de-

crease the superheat, turn the stem counterclockwise.

Do not turn the stem more than one full turn.

3. Wait until suction pressure and superheat stabilize.

This may take more than 30 minutes.

4. Continue adjustment until superheat reaches 10_F to

15_F (5.5_C to 8.3_C).

5. Replace the seal cap; tighten.

INSTALLER / INSTALLATEUR

TXV superheat must be checked at initial
unit start-up and adjusted if necessary.
Superheat must be 10 - 15 deg F.

La surchauffe TXV doit être vérifiée au
moment de la mise en route initiale et
ajustée si nécessaire. La surchauffe doit
être comprise entre 10 et 15 degrés F.

40RU500073 2.0

C10828

Fig. 21 -- Label, TXV Adjustment

SERVICE

Inspection and maintenance should be performed at

regular intervals and should include the following:

S

Complete cleaning of cabinet, fan wheel, cooling coil,
condensate pan and drain, heating coils, and return--air
grille (if present).

S

Inspection of panels and sealing of unit against air
leakage.

S

Adjustment of fan motor, belt, bearings, and wheels.

S

Cleaning or replacement of filters.

S

Testing for cooling/heating system leaks.

S

Checking of all electrical connections.

ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal

injury or death.
Before performing service or maintenance operations

on unit, always turn off main power switch to unit and

install lockout tag. Unit may have more than one

power switch.

!

WARNING

Most unit service can be performed by removing one or

both of the unit’s side panels. Coil cleaning or removal or

insulation cleaning may require removal of a rear, top, or

bottom panel, depending on the unit’s orientation. When

service is completed, replace unit panels.

Panels -- Panels are fastened to unit frame with sheet

metal screws. Fan and coil compartment must be sealed

tightly after service to prevent air from bypassing the

cooling coil.

524J