Basic display group parameters – Rockwell Automation 25B PowerFlex 520-Series Adjustable Frequency AC Drive Quick Start User Manual

Page 18

Advertising
background image

18

Rockwell Automation Publication 520-QS001A-EN-E - March 2014

PowerFlex 520-Series Adjustable Frequency AC Drive

Basic Display Group Parameters

See the PowerFlex 520-Series Adjustable Frequency AC Drive User Manual, publication

520-UM001

for detailed

descriptions of the parameters listed here, as well as the full list of available parameters.

No.

Parameter

Min/Max

Display/Options

b001

[Output Freq]

0.00/[Maximum Freq]

0.01 Hz

Output frequency present at T1, T2 & T3 (U, V & W). Does not include slip frequency.

b002

[Commanded Freq]

0.00/[Maximum Freq]

0.01 Hz

Value of the active frequency command even if the drive is not running.
Important: The frequency command can come from a number of sources.

b003

[Output Current]

0.00/(Drive Rated Amps x 2)

0.01 A

Output current present at T1, T2 & T3 (U, V & W).

b004

[Output Voltage]

0.0/Drive Rated Volts

0.1V

Output voltage present at T1, T2 & T3 (U, V & W).

b005

[DC Bus Voltage]

0/1200VDC

1VDC

Filtered DC bus voltage level of the drive.

b006

[Drive Status]

00000/11111

Digit 5

Digit 4

Digit 3

Digit 2

Digit 1

SafetyActive

(1)

Decelerating Accelerating Forward

Running

Present operating condition of the drive.

(1) Setting is specific to PowerFlex 525 drives only.

b007,
b008,
b009

[Fault x Code]

F0/F127

F0

A code that represents a drive fault. Codes appear in these parameters in the order they occur (b007
[Fault 1 Code] = the most recent fault). Repetitive faults are only recorded once.
See Fault and Diagnostic Group for more information.

b010

[Process Display]

0/9999

1

Output frequency scaled by [Process Disp Hi] and [Process Disp Lo].

b0012

[Control Source]

0000/2165

Digit 4, 3, & 2

Digit 1

Freq Command Source

Start Command Source

Active source of the Start Command and Frequency Command. Normally defined by the settings of
P046, P048, P050 [Start Source x] and P047, P049, P051 [Speed Referencex].

b013

[Contrl In Status]

0000/1111

Digit 4

Digit 3

Digit 2

Digit 1

DB Trans On

(1)

DigIn TBlk 3 DigIn TBlk 2 DigIn TBlk 1

State of the digital terminal blocks 1...3 and DB transistor.
Important: Actual control commands may come from a source other than the control terminal block.

(1) Setting is specific to PowerFlex 525 drives only.

b014

[Dig In Status]

0000/1111

Digit 4

Digit 3

Digit 2

Digit 1

DigIn TBlk 8

(1)

DigIn TBlk 7

(1)

DigIn TBlk 6 DigIn TBlk 5

State of the programmable digital inputs.

(1) Setting is specific to PowerFlex 525 drives only.

b015

[Output RPM]

0/24000 rpm

1 rpm

Current output frequency in rpm. Scale is based on P035 [Motor NP Poles].

b016

[Output Speed]

0.0/100.0%

0.1%

Current output frequency in %. Scale is 0% at 0.00 Hz to 100% at P044 [Maximum Freq].

b017

[Output Power]

0.00/(Drive Rated Power x 2)

0.01 kW

Output power present at T1, T2 & T3 (U, V & W).

b018

[Power Saved]

0.00/655.35 kW

0.01 kW

Instantaneous power savings of using this drive compared to an across the line starter.

b019

[Elapsed Run time]

0/65535 x 10 hr

1 = 10 hr

Accumulated time drive is outputting power. Time is displayed in 10 hour increments.

b020

[Average Power]

0.00/(Drive Rated Power x 2)

0.01 kW

Average power used by the motor since the last reset of the meters.

b021

[Elapsed kWh]

0.0/100.0 kWh

0.1 kWh

Accumulated output energy of the drive. When the maximum value of this parameter is reached, it
resets to zero and b022 [Elapsed MWh] is incremented.

Advertising