PowerFlex 520-Series Adjustable Frequency AC Drive

A466

A478

[PID x Preload]

0.0/500.0 Hz

0.1 Hz

0.0 Hz

Sets the value used to preload the integral component on start or enable.

A467

A479

[PID x Invert Err]

0/1

0 = “Normal”
1 = “Inverted”

0 = “Normal”

Changes the sign of the PID error.

A481

[Process Disp Lo]

0.00/99.99

0.01

0.00

Sets the value displayed in b010 [Process Display] when the drive is running at P043 [Minimum Freq].

A482

[Process Disp Hi]

0.00/99.99

0.01

0.00

Sets the value displayed in b010 [Process Display] when the drive is running at P044 [Maximum Freq].

A483

[Testpoint Sel]

0/FFFF

1

400

Used by Rockwell Automation field service personnel.

A484

[Current Limit 1]

0.0/Drive Rated Amps x 1.5 (Normal Duty); Drive
Rated Amps x 1.8 (Heavy Duty)

0.1 A

Drive Rated Amps x 1.1
(Normal Duty); Drive Rated
Amps x 1.5 (Heavy Duty)

Maximum output current allowed before current limiting occurs.

A485

[Current Limit 2]

0.0/Drive Rated Amps x 1.5 (Normal Duty); Drive
Rated Amps x 1.8 (Heavy Duty)

0.1 A

Drive Rated Amps x 1.1

Maximum output current allowed before current limiting occurs.

A486

A488

[Shear Pinx Level]

0.0/(Drive Rated Amps x 2)

0.1 A

0.0 A (Disabled)

Sets the value of current at which the shear pin fault occurs after the time set in A487, A489 [Shear Pin x
Time]. Setting the value at 0.0 A disables this function.

A487

A489

[Shear Pin x Time]

0.00/30.00 s

0.01 s

0.00 s

Sets the continuous time the drive must be at or above the value set in A486, A488 [Shear Pinx Level]
before a shear pin fault occurs.

A490

[Load Loss Level]

0.0/Drive Rated Amps

0.1 A

0.0 A

Provides a software trip (Load Loss fault) when the current drops below this level for the time specified in
A491 [Load Loss Time].

A491

[Load Loss Time]

0/9999 s

1 s

0 s

Sets the required time for the current to be below A490 [Load Loss Level] before a Load Loss fault occurs

A492

[Stall Fault Time]

0/5

0 = “60 Seconds”
1 = “120 Seconds”
2 = “240 Seconds”
3 = “360 Seconds”
4 = “480 Seconds”
5 = “Flt Disabled”

0 = “60 Seconds”

Sets the time that the drive remains in stall mode before a fault is issued.

A493

[Motor OL Select]

0/2

0 = “No Derate”
1 = “Min. Derate”
2 = “Max. Derate”

0 = “No Derate”

Drive provides Class 10 overload protection. Settings 0...2 select the derating factor for the I

2

t overload

function.

A494

[Motor OL Ret]

0/1

0 = “Reset”
1 = “Save”

0 = “Reset

Selects whether the motor overload counter is saved on power-down or reset on power-up.

A495

[Drive OL Mode]

0/3

0 = “Disabled”
1 = “Reduce CLim”
2 = “Reduce PWM”
3 = “Both-PWM 1st”

3 = “Both-PWM 1st”

Determines how the drive handles overload conditions that would otherwise cause the drive to fault.

A496

[IR Voltage Drop]

0.0/600.0VAC

0.1VAC

Based on Drive Rating

Value of volts dropped across the resistance of the motor stator (autotune) for induction motor.

A497

[Flux Current Ref]

0.00/(Drive Rated Amps x 1.4)

0.01 A

Based on Drive Rating

This is the current necessary for full motor flux. The value should be set to the full speed no-load current of
the motor.

= Stop drive before changing this parameter.
= Parameter is specific to PowerFlex 525 drives only.

No.

Parameter

Min/Max

Display/Options

Default

PF 525

PF 525

PF 525

PF 525

PF 525

PF 525

PF 525

PF 525