Technical specifications, Powerflex 523 specifications, Powerflex 525 specifications – Rockwell Automation 25B PowerFlex 520-Series Adjustable Frequency AC Drive Quick Start User Manual

Page 8

Advertising
background image

8

Rockwell Automation Publication 520-QS001A-EN-E - March 2014

PowerFlex 520-Series Adjustable Frequency AC Drive

Technical Specifications

PowerFlex 523 Specifications

Input/Output Ratings

Digital Control Inputs (Input Current = 6 mA)

Approvals

Output Frequency: 0...500 Hz (Programmable)
Efficiency: 97.5% (Typical)

SRC (Source) Mode:

18...24V = ON
0...6V = OFF

SNK (Sink) Mode:

0...6V = ON
18...24V = OFF

Control Output

Analog Control Inputs

Fuses and Circuit Breakers

Programmable Output, Form C
Resistive Rating: 3.0 A @ 30V DC, 125V AC and 240V AC
Inductive Rating: 0.5 A @ 30V DC, 125V AC and 240V AC

4-20 mA Analog: 250

Ω

input impedance

0-10V DC Analog: 100 k

Ω

input impedance

External Pot: 1...10 k

Ω

, 2 W min.

Recommended Fuse Type:

UL Class CC, J, T or Type BS88; 600V (550V) or equivalent.

Recommended Circuit Breakers: HMCP or equivalent.

Protective Features

Motor Protection: I

2

t overload protection – 150% for 60 s, 200% for 3 s (Provides Class 10 protection)

Overcurrent: 200% hardware limit, 300% instantaneous fault

Over Voltage: 100...120V AC Input – Trip occurs @ 405V DC bus voltage (equivalent to 150V AC incoming line)

200...240V AC Input – Trip occurs @ 405V DC bus voltage (equivalent to 290V AC incoming line)
380...480V AC Input – Trip occurs @ 810V DC bus voltage (equivalent to 575V AC incoming line)
525...600V AC Input – Trip occurs @ 1005V DC bus voltage (equivalent to 711V AC incoming line)

Under Voltage: 100...120V AC Input – Trip occurs @ 190V DC bus voltage (equivalent to 75V AC incoming line)

200...240V AC Input – Trip occurs @ 190V DC bus voltage (equivalent to 150V AC incoming line)
380...480V AC Input – Trip occurs @ 390V DC bus voltage (equivalent to 275V AC incoming line)
525...600V AC Input – If P038 = 3 “600V” trip occurs @ 487V DC bus voltage (344V AC incoming line);

– If P038 = 2 “480V” trip occurs @ 390V DC bus voltage (275V AC incoming line)

Control Ride Through: Minimum ride through is 0.5 s - typical value 2 s

Faultless Power Ride Through: 100 ms

PowerFlex 525 Specifications

Input/Output Ratings

Approvals

Output Frequency: 0...500 Hz (Programmable)
Efficiency: 97.5% (Typical)

Digital Control Inputs (Input Current = 6 mA)

Analog Control Inputs

Fuses and Circuit Breakers

SRC (Source) Mode:

18...24V = ON
0...6V = OFF

SNK (Sink) Mode:

0...6V = ON
18...24V = OFF

4-20 mA Analog: 250

Ω

input impedance

0-10V DC Analog: 100 k

Ω

input impedance

External Pot: 1...10 k

Ω

, 2 W min.

Recommended Fuse Type:

UL Class J, T or Type BS88; 600V (550V) or equivalent.

Recommended Circuit Breakers: HMCP or equivalent.

Control Output

Programmable Output, Form A and Form B
Resistive Rating: 3.0 A @ 30V DC, 125V AC and 240V AC
Inductive Rating: 0.5 A @ 30V DC, 125V AC and 240V AC

Opto Outputs
30V DC, 50 mA
Non-inductive

Analog Outputs (10-bit)
0-10V: 1 k

Ω

min.

4-20 mA: 525

Ω

max.

Protective Features

Motor Protection: I

2

t overload protection – 150% for 60 s, 200% for 3 s (Provides Class 10 protection)

Overcurrent: 200% hardware limit, 300% instantaneous fault

Over Voltage: 100...120V AC Input – Trip occurs @ 405V DC bus voltage (equivalent to 150V AC incoming line)

200...240V AC Input – Trip occurs @ 405V DC bus voltage (equivalent to 290V AC incoming line)
380...480V AC Input – Trip occurs @ 810V DC bus voltage (equivalent to 575V AC incoming line)
525...600V AC Input – Trip occurs @ 1005V DC bus voltage (equivalent to 711V AC incoming line)

Under Voltage: 100...120V AC Input – Trip occurs @ 190V DC bus voltage (equivalent to 75V AC incoming line)

200...240V AC Input – Trip occurs @ 190V DC bus voltage (equivalent to 150V AC incoming line)
380...480V AC Input – Trip occurs @ 390V DC bus voltage (equivalent to 275V AC incoming line)
525...600V AC Input – If P038 = 3 “600V” trip occurs @ 487V DC bus voltage (344V AC incoming line);

– If P038 = 2 “480V” trip occurs @ 390V DC bus voltage (275V AC incoming line)

Control Ride Through: Minimum ride through is 0.5 s – typical value 2 s

Faultless Power Ride Through: 100 ms

UL

®

LIS

TED 966X

IN

D CONT EQ

UL508C

UL

®

LIS

TED 966X

IN

D CO NT EQ

C

CSA 22.2

LV Directive 2006/95/EC: EN 61800-5-1

EMC Directive 2004/108/EC: EN 61800-3:2004

N223

AC156

KCC: Article 58-2 of Radio Waves Act, Clause 3
GOST-R: POCC US.ME92.H00040

UL

®

LIS

TED 966X

IN

D CONT EQ

UL508C

UL

®

LIS

TED 966X

IN

D CO NT EQ

C

CSA 22.2

LV Directive 2006/95/EC: EN 61800-5-1

EMC Directive 2004/108/EC: EN 61800-3:2004

N223

AC156

KCC: Article 58-2 of Radio Waves Act, Clause 3
GOST-R: POCC US.ME92.H00040

TUV

Rheinland

.

.

Functional

Safety

Bauart geprüft

Type approved

II (2) G D

Advertising
This manual is related to the following products: