Power wiring – Rockwell Automation 25B PowerFlex 520-Series Adjustable Frequency AC Drive Quick Start User Manual

Page 9

Advertising
background image

Rockwell Automation Publication 520-QS001A-EN-E - March 2014

9

PowerFlex 520-Series Adjustable Frequency AC Drive

Power Wiring

Power Terminal Block Diagrams and Wiring Specifications

Recommended Shielded Wire

Location

Rating/Type

Description

Standard (Option 1)

600V, 90 °C (194 °F) XHHW2/RHW-2
Anixter B209500-B209507, Belden 29501-29507, or equivalent

Four tinned copper conductors with XLPE insulation.
Copper braid/aluminum foil combination shield and tinned copper drain wire.
PVC jacket.

Standard (Option 2)

Tray rated 600V, 90 °C (194 °F)
RHH/RHW-2 Anixter OLF-7xxxxx or equivalent

Three tinned copper conductors with XLPE insulation.
5 mil single helical copper tape (25% overlap min.) with three bare copper grounds

in contact with shield.

PVC jacket.

Class I & II; Division I & II

Tray rated 600V, 90 °C (194 °F)
RHH/RHW-2 Anixter 7V-7xxxx-3G or equivalent

Three bare copper conductors with XLPE insulation and impervious corrugated

continuously welded aluminum armor.

Black sunlight resistant PVC jacket overall.
Three copper grounds on #10 AWG and smaller.

Input Power Conditions

Input Power Condition

Corrective Action

Low Line Impedance (less than 1% line reactance)

Install Line Reactor

(2)

or Isolation Transformer

(2) See Appendix B of the PowerFlex 520-Series Adjustable Frequency AC Drive User Manual, publication

520-UM001

for accessory ordering information.

Greater than 120 kVA supply transformer

Line has power factor correction capacitors

Install Line Reactor

(2)

or Isolation Transformer

Line has frequent power interruptions

Line has intermittent noise spikes in excess of 6000V (lightning)

Phase to ground voltage exceeds 125% of normal line to line voltage

Remove MOV jumper to ground.
or Install Isolation Transformer with grounded secondary if necessary.

Ungrounded distribution system

240V open delta configuration (stinger leg)

(1)

(1) For drives applied on an open delta with a middle phase grounded neutral system, the phase opposite the phase that is tapped in the middle to the neutral or earth is referred to as the “stinger leg,” “high

leg,” “red leg,” etc. This leg should be identified throughout the system with red or orange tape on the wire at each connection point. The stinger leg should be connected to the center Phase B on the
reactor. See Appendix B of the PowerFlex 520-Series Adjustable Frequency AC Drive User Manual, publication

520-UM001

for specific line reactor part numbers.

Install Line Reactor

(2)

V/T2

T/L3

S/L2

R/L1

U/T1

W/T3

BR+

BR-

DC- DC+

V/T2

T/L3

S/L2

R/L1

U/T1

W/T3

BR+

BR-

DC-

DC+

Frame A...D

Frame E

Terminal

Description

R/L1, S/L2

1-Phase Input Line Voltage Connection

R/L1, S/L2, T/L3

3-Phase Input Line Voltage Connection

U/T1, V/T2, W/T3

Motor Phase
Connection =

Switch any two motor leads to change
forward direction.

DC+, DC-

DC Bus Connection (except for 110V 1-Phase)

BR+, BR-

Dynamic Brake Resistor Connection

Safety Ground – PE

Frame

Maximum Wire Size

(1)

(1) Maximum/minimum sizes that the terminal block will accept – these are not recommendations.

Minimum Wire Size

(1)

Torque

A

5.3 mm

2

(10 AWG)

0.8 mm

2

(18 AWG)

1.76...2.16 Nm (15.6...19.1 lb-in.)

B

8.4 mm

2

(8 AWG)

2.1 mm

2

(14 AWG)

1.76...2.16 Nm (15.6...19.1 lb-in.)

C

8.4 mm

2

(8 AWG)

2.1 mm

2

(14 AWG)

1.76...2.16 Nm (15.6...19.1 lb-in.)

D

13.3 mm

2

(6 AWG)

5.3 mm

2

(10 AWG)

1.76...2.16 Nm (15.6...19.1 lb-in.)

E

26.7 mm

2

(3 AWG)

8.4 mm

2

(8 AWG)

3.09...3.77 Nm (27.3...33.4 lb-in.)