PowerFlex 520-Series Adjustable Frequency AC Drive

F033

Auto Rstrt Tries

Correct the cause of the fault and manually clear.

F038

Phase U to Gnd

Check the wiring between the drive and motor.
Check motor for grounded phase.
Replace drive if fault cannot be cleared.

F039

Phase V to Gnd

F040

Phase W to Gnd

F041

Phase UV Short

Check the motor and drive output terminal wiring for a shorted condition.
Replace drive if fault cannot be cleared.

F042

Phase UW Short

F043

Phase VW Short

F048

Params Defaulted

Clear the fault or cycle power to the drive.
Program the drive parameters as needed.

F059

(1)

Safety Open

Check safety input signals. If not using safety, verify and tighten jumper for I/O terminals S1, S2 and S+.

F063

SW OverCurrent

Verify connections between motor and load.
Verify level and time requirements.

F064

Drive Overload

Reduce load or extend Accel Time.

F070

Power Unit

Check maximum ambient temperature has not been exceeded.
Cycle power.
Replace drive if fault cannot be cleared.

F071

DSI Net Loss

Cycle power.
Check communications cabling.
Check Modbus or DSI setting.
Check Modbus or DSI status.

F072

Opt Net Loss

Cycle power.
Check communications cabling.
Check network adapter setting.
Check external network status.

F073

(1)

EN Net Loss

Cycle power.
Check communications cabling.
Check EtherNet/IP setting.
Check external network status.

F080

Autotune Failure

Restart procedure.

F081

DSI Comm Loss

Cycle power.
Check communications cabling.
Check Modbus or DSI setting.
Check Modbus or DSI status.
Modify using C125 [Comm Loss Action].
Connecting I/O terminals C1 and C2 to ground may improve noise immunity.
Replace wiring, Modbus master device, or control module.

F082

Opt Comm Loss

Cycle power.
Reinstall option card in drive.
Modify using C125 [Comm Loss Action].
Replace wiring, port expander, option card, or control module.

F083

(1)

EN Comm Loss

Cycle power.
Check EtherNet/IP setting.
Check drive’s Ethernet settings and diagnostic parameters.
Modify using C125 [Comm Loss Action].
Replace wiring, Ethernet switch, or control module.

F091

(1)

Encoder Loss

Check Wiring.
If P047, P049, P051 [Speed Referencex] = 16 “Positioning” and A535 [Motor Fdbk Type] = 5 “Quad Check”, swap the Encoder channel inputs or

swap any two motor leads.

Replace encoder.

F094

Function Loss

Close input to the terminal and cycle power.

F100

Parameter Chksum

Set P053 [Reset To Defalts] to 2 “Factory Rset”.

F101

External Storage

Set P053 [Reset To Defalts] to 2 “Factory Rset”.

F105

C Connect Err

Clear fault and verify all parameter settings. Do not remove or install the control module while power is applied.

F106

Incompat C-P

Change to a different power module.
Change to a PowerFlex 523 control module.

F107

Replaced C-P

Change to a different power module.
Replace control module if changing power module does not work.

No.

Fault

Action