Rockwell Automation Publication 520-QS001A-EN-E - March 2014

33

PowerFlex 520-Series Adjustable Frequency AC Drive

Network Communication

PowerFlex 520-Series RS784 (DSI) Protocol

This section contains only basic information to setup the PowerFlex 520-series RS485 (DSI) protocol connection with
your PowerFlex 520-series drive. See the PowerFlex 520-Series Adjustable Frequency AC Drive User Manual, publication

520-UM001

for more information.

PowerFlex 520-series drives support the RS485 (DSI) protocol to allow efficient operation with Rockwell Automation
peripherals. In addition, some Modbus functions are supported to allow simple networking. PowerFlex 520-series drives
can be multi-dropped on an RS485 network using Modbus protocol in RTU mode.

PowerFlex 520-Series Drive Network

Network Wiring

Network wiring consists of a shielded 2-conductor cable that is daisy-chained from node to node.

Network Wiring Diagram Example

ATTENTION: Never attempt to connect a Power over Ethernet (PoE) cable to the RS485 port. Doing so may damage the circuitry.

IMPORTANT

The shield is connected at ONLY ONE end of each cable segment.

Esc

Sel

Esc

Sel

Esc

Sel

Esc

Sel

Controller

PowerFlex 520-Series Drives

C1 C2

Master

4

5

TxRxD-

TxRxD+

TxRxD-

TxRxD+

TxRxD-

TxRxD+

Shield

Shield

Shield

120 ohm resistor

120 ohm resistor

X

X

X

FRONT

PIN 8

PIN 1

TxRxD-

TxRxD+

RS485

(DSI)

AK-U0-RJ45-TB2P

V/T2

T/L3

S/L2

R/L1

U/T1

W/T3

BR+

BR-

DC- DC+

C1 C2

TxRxD-

TxRxD+

RS485

(DSI)

V/T2

T/L3

S/L2

R/L1

U/T1

W/T3

BR+

BR-

DC- DC+

PowerFlex 525

Node 1

4

5

PowerFlex 523

Node 2

4

5

PowerFlex 525

Node “n”

Advertising