Smart Start-Up with Basic Program Group Parameters

The PowerFlex 520-series drive is designed so that start-up is simple and efficient. The Basic Program group contains the
most commonly used parameters. See the PowerFlex 520-Series Adjustable Frequency AC Drive User Manual, publication

520-UM001

for detailed descriptions of the parameters listed here, as well as the full list of available parameters.

= Stop drive before changing this parameter.
= Parameter is specific to PowerFlex 525 drives only.

No.

Parameter

Min/Max

Display/Options

Default

P030

[Language]

1/15

1 = English
2 = Français
3 = Español
4 = Italiano
5 = Deutsch
6 = Reserved
7 = Português
8 = Reserved
9 = Reserved
10 = Reserved
11 = Reserved
12 = Polish
13 = Reserved
14 = Turkish
15 = Czech

1

Selects the language displayed.
Important: The setting takes effect after the drive is power cycled.

P031

[Motor NP Volts]

10V (for 200V Drives), 20V (for 400V Drives),
25V (for 600V Drives) / Drive Rated Volts

1V

Based on Drive Rating

Sets the motor nameplate rated volts.

P032

[Motor NP Hertz]

15/500 Hz

0.1 A

60 Hz

Sets the motor nameplate rated frequency.

P033

[Motor OL Current]

0.0/(Drive Rated Amps x 2)

0.1 A

Based on Drive Rating

Sets the motor nameplate overload current.

P034

[Motor NP FLA]

0.0/(Drive Rated Amps x 2)

0.1 A

Drive Rated Amps

Sets the motor nameplate FLA.

P035

[Motor NP Poles]

2/40

1

4

Sets the number of poles in the motor.

P036

[Motor NP RPM]

0/24000 rpm

1 rpm

1750 rpm

Sets the rated nameplate rpm of motor.

P037

[Motor NP Power]

0.00/Drive Rated Power

0.01 kW

Drive Rated Power

Sets the motor nameplate power. Used in PM regulator.

P038

[Voltage Class]

2/3

2 = “480V”
3 = “600V”

3

Sets the voltage class of 600V drives. Only applicable to 600V drives.

P039

[Torque Perf Mode]

0/3

0 = “V/Hz”
1 = “SVC”
2 = “Economize”
3 = “Vector”

(1)

1

Selects the motor control mode.

(1) Setting is specific to PowerFlex 525 drives only.

P040

[Autotune]

0/2

0 = “Ready/Idle”
1 = “Static Tune”
2 = “Rotate Tune”

0

Enables a static (not spinning) or dynamic (motor spinning) autotune.

P041

[Accel Time 1]

0.00/600.00 s

0.01 s

10.00 s

Sets the time for the drive to accel from 0 Hz to
[Maximum Freq].

P042

[Decel Time 1]

0.00/600.00 s

0.01 s

10.00 s

Sets the time for the drive to decel from [Maximum
Freq] to 0 Hz.