Rockwell Automation 25B PowerFlex 520-Series Adjustable Frequency AC Drive Quick Start User Manual

Page 24

Advertising
background image

24

Rockwell Automation Publication 520-QS001A-EN-E - March 2014

PowerFlex 520-Series Adjustable Frequency AC Drive

A458

A470

[PID x Trim Sel]

0/13

0 = “Disabled”
1 = “TrimOn Pot”
2 = “TrimOn Keypd”
3 = “TrimOn DSI”
4 = “TrimOn NetOp”
5 = “TrimOn 0-10V”
6 = “TrimOn 4-20”
7 = “TrimOn Prset”
8 = “TrimOn AnMlt”

(1)

9 = “TrimOn MOP”
10 = “TrimOn Pulse”
11 = “TrimOn Slgic”

(1)

12 = “TrimOn Encdr”

(1)

13 = “TrimOn ENet”

(1)

0 = “Disabled”

Sets the PID output as trim to the source reference.

(1) Setting is specific to PowerFlex 525 drives only.

A459

A471

[PID x Ref Sel]

0/13

0 = “PID Setpoint”
1 = “Drive Pot”
2 = “Keypad Freq”
3 = “Serial/DSI”
4 = “Network Opt”
5 = “0-10V Input”
6 = “4-20mA Input”
7 = “Preset Freq”
8 = “AnlgIn Multi”

(1)

9 = “MOP Freq”
10 = “Pulse Input”
11 = “Step Logic”

(1)

12 = “Encoder”

(1)

13 = “EtherNet/IP”

(1)

0 = “PID Setpoint”

Selects the source of the PID reference.

(1) Setting is specific to PowerFlex 525 drives only.

A460

A472

[PID x Fdback Sel]

0/6

0 = “0-10V Input”
1 = “4-20mA Input”
2 = “Serial/DSI”
3 = “Network Opt”
4 = “Pulse Input”
5 = “Encoder”

(1)

6 = “EtherNet/IP”

(1)

0 = “0-10V Input”

Selects the source of the PID feedback.

(1) Setting is specific to PowerFlex 525 drives only.

A461

A473

[PID x Prop Gain]

0.00/99.99

0.01

0.01

Sets the value for the PID proportional component when the PID mode is enabled.

A462

A474

[PID x Integ Time]

0.0/999.9 s

0.1 s

2.0 s

Sets the value for the PID integral component when PID mode is enabled.

A463

A475

[PID x Diff Rate]

0.00/99.99

0.01

0.00

Sets the value (in 1/second) for the PID differential component when PID mode is enabled.

A464

A476

[PID x Setpoint]

0.0/100.0%

0.1%

0.0%

Provides an internal fixed value for process setpoint when PID mode is enabled.

A465

A477

[PID x Deadband]

0.0/10.0%

0.1%

0.0%

Sets the lower limit of the PID output.

= Stop drive before changing this parameter.
= Parameter is specific to PowerFlex 525 drives only.

No.

Parameter

Min/Max

Display/Options

Default

PF 525

PF 525

PF 525

PF 525

PF 525

PF 525

PF 525

PF 525

PF 525