Rockwell Automation 1502 Medium Voltage 400A Contactor - Series E User Manual

Page 11

Advertising
background image

Rockwell Automation Publication 1502-UM052H-EN-P - June 2013

11

Product Description

Chapter 1

Operational Characteristics

Mechanical Life (Operations) x 1000

(4)

Electrically Held

2500

Mechanical Latch

100

Electrical Life (Operations) x 1000

(4)

1000

Switching Frequency (Operations per hour)

Electrically Held

600

Mechanical Latch

150

Opening and Closing Times

Electro-Mechanical (Relay) Control (Mechanical Latch Only)

Maximum Closing Time (120 VAC)

50 or 60 Hz (milliseconds)

160

Maximum Opening Time (120 VAC)

50 or 60 Hz (milliseconds)

50

IntelliVAC and IntelliVAC Plus Control (Electrically Held & Mechanical Latch)

Maximum Closing Time (50 to 60 Hz)

120 / 240 VAC (milliseconds)

100 / 70

Maximum Opening Time
(without delay, for 50 to 60 Hz)

(5)

120 to 240 VAC (milliseconds)

60

Capacitor Switching (max. KVAR)

System Voltage

2400V

800

4160V

1400

6900V

2000

General

Standard Altitude Capability (meters / feet)

(1)(6)

-1000...5000 / 3300...16,500

Contactor Weight (kg / lbs)

21.8 / 48

Auxiliary Contact Rating

A600

Auxiliary Contacts on the Vacuum Contactor (Max.)

(7)

3 N.O. / 3 N.C.

(1) The voltage and current ratings listed are valid up to 1,000 m (3,300 ft). Please refer to

Table 3

for ratings above this altitude.

(2) The IEC rating at 7200V (RMS Sym.) is 5300 A / 66 MVA.
(3) Control voltage, as measured at the input of the IntelliVAC or IntelliVAC Plus control module.
(4) Provided that regular maintenance is performed, as detailed in this manual.
(5) A contactor drop-out delay may be configured with the IntelliVAC or IntelliVAC Plus control module (refer to publications

1503-UM053_-EN-P

and

1503-UM054_-

EN-P

).

(6) The full Altitude range is available with the IntelliVAC or IntelliVAC Plus control module only, and the IntelliVAC or IntelliVAC Plus is to be configured accordingly (refer

to publications

1503-UM053_-EN-P

and

1503-UM054_-EN-P

). The standard mechanical latch contactors, if used with electro-mechanical control, are designed

for -1000...1000 m (-3300...3300 ft). Higher altitudes are possible by changing the contactor return springs (refer to

Figure 5

for suitable catalog numbers).

(7) The number of contactor auxiliary contacts depends on the contactor type. Some of the contacts are used in the typical control schemes used.

Table 2 - Bulletin 1502 Medium Voltage 400 Amp Contactor Ratings (Continued)

Advertising