Product Approvals

UL347
CSA22.2 No. 14 and T.I.L. D-21
IEC60470
CE Mark

Table 3 - Altitude Derating

Altitude Rating

Reduce Max. Continuous Current Rating By:

Reduce B.I.L. Withstand Rating by:

400 A

800 A

0...1000 m (0...3300 ft)

1001...2000 m (3301...6600 ft)

10 A

20 A

6.0 kV

2001...3000 m (6601...9900 ft)

20 A

40 A

12.0 kV

3001...4000 m (9901...13,200 ft)

30 A

60 A

18.0 kV

4001...5000 m (13,201...16,500 ft)

40 A

80 A

24.0 kV