Product approvals – Rockwell Automation 1502 Medium Voltage 400A Contactor - Series E User Manual
Page 12
Advertising
12
Rockwell Automation Publication 1502-UM052H-EN-P - June 2013
Chapter 1
Product Description
Product Approvals
• UL347
• CSA22.2 No. 14 and T.I.L. D-21
• IEC60470
• CE Mark
Table 3 - Altitude Derating
Altitude Rating
Reduce Max. Continuous Current Rating By:
Reduce B.I.L. Withstand Rating by:
400 A
800 A
0...1000 m (0...3300 ft)
–
–
–
1001...2000 m (3301...6600 ft)
10 A
20 A
6.0 kV
2001...3000 m (6601...9900 ft)
20 A
40 A
12.0 kV
3001...4000 m (9901...13,200 ft)
30 A
60 A
18.0 kV
4001...5000 m (13,201...16,500 ft)
40 A
80 A
24.0 kV