Maintenance

Chapter 4

2. Using ½” wrench, remove the auxiliary contact actuator plate form the

main shaft assembly (

Figure 42

).

Figure 42 - Auxiliary Actuator Plate Removal

3. Using two 7/16” wrenches, loosen the auxiliary contact assembly retaining

bolt and slide the auxiliary contact assembly out of the front of the
contactor (

Figure 43

).

Figure 43 - Auxiliary Contact Assembly Removal

4. Disconnect the mechanical latch trip coil leads form the auxiliary contact

assembly using a Phillips screwdriver.

5. Using a 3/8” socket, remove the ¼-20 hardware holding the mechanical

trip mechanism in place, and then remove the mechanical trip mechanism
(

Figure 44

).

Actuator Plate

Auxiliary Contact

Assembly

Retaining Bolt

Advertising