Coil replacement procedure, Figure 32 – Rockwell Automation 1502 Medium Voltage 400A Contactor - Series E User Manual

Page 42

Advertising
background image

42

Rockwell Automation Publication 1502-UM052H-EN-P - June 2013

Chapter 4

Maintenance

Figure 32 - Contact Gap Adjustment

Coil Replacement Procedure

Refer to Chapter 6 for the part number(s) required for this procedure.

1. Remove the auxiliary actuator, front stop bracket and armature plate as

shown in

Figure 33

.

Do not remove the bolts which secure the stop bracket, simply loosen them
and slide the bracket out.

Stop Bracket Bolts

Gap Adjustment Screw

Gap Adjustment Screw
Locking Nut

Stop Bracket

ATTENTION: To avoid shock hazards, lock out incoming power and disconnect
the control plug from the contactor before working on the unit. Verify with a hot
stick or meter that all circuits are voltage free. Failure to do so may result in
severe burns, injury or death.

Advertising