Rockwell Automation 1502 Medium Voltage 400A Contactor - Series E User Manual

Page 43

Advertising
background image

Rockwell Automation Publication 1502-UM052H-EN-P - June 2013

43

Maintenance

Chapter 4

Figure 33 - Access to Coils

2. Remove the retaining ring from the core of the coil you wish to replace as

shown in

Figure 34

.

3. Loosen the auxiliary assembly retaining bolt and slide the assembly and the

coils forward and out of the contactor as shown in

Figure 34

.

Figure 34 - Coil Removal

4. Disconnect the coil leads (take note of their location). Connect the leads

of the new coil making sure that all metal-oxide varistors (MOVs) and/or
diodes are secure. Refer to the appropriate wiring diagram in this manual if
further control wiring details are required (see

page 20

).

5. Slide the new coil into position and install the retaining ring on the core.

Install the auxiliary assembly leaving the retaining bolt loose for adjustment
later. See the Auxiliary Contact Set-up Procedure (page 4-10) for
determining the position of the auxiliary assembly.

Auxiliary Actuator

Stop Bracket Bolts

Armature Stop Bracket

Armature Plate

Return Spring Actuator Plate

Grade 5 (5/16 Hardware) to mount
return spring actuator plate. Refer
to page 4-1 for torque values.

Grade 5 (5/16 Hardware) to mount
armature plate. Refer to page 4-1
for torque values.

Auxiliary Assembly

Retaining Bolt

Operating Coil

Operating Coil

Retaining Ring

Auxiliary Assembly

Advertising