Rockwell Automation 1502 Medium Voltage 400A Contactor - Series E User Manual

Page 51

Advertising
background image

Rockwell Automation Publication 1502-UM052H-EN-P - June 2013

51

Maintenance

Chapter 4

8. Remove the flapper by sliding it to the right until it stops and then pulling

it towards the front of the contact (

Figure 47

). The trip (magnet) coil and

coil core are now exposed (

Note: Contactor not shown for clarity).

Figure 47 - Removal of Flapper

9. Using a right angle Allen key, remove the coil core (

Figure 48

) and trip

(magnet) coil (

Note: Contactor not shown for clarity).

Figure 48 - Trip Coil and Core Removal

10. Slide the coil core from the trip (magnet) coil and then place the

replacement coil onto the coil core.

11. Connect the new trip (magnet) coil leads to the auxiliary contact assembly.
12. Re-assemble the mechanical latch and auxiliary assembly in reverse order

of this procedure.

13. Perform the auxiliary contact assembly adjustment procedure (see

page 44

).

Note: The contactor will not function correctly if this step is not

performed.

14. Verify that the replacement trip coil functions by using Test Power to close

(latch) the contactor. Complete the cycle by opening (tripping) the
contactor. Perform this sequence 2-3 times to ensure that the contactor
closes (latches and opens (trips) properly.

Flapper

Step 1:
Slide flapper to right.

Step 2:
Pull flapper forward to remove.

Magnet Coil

Coil Core

Use right angle Allen key
to remove coil core