Rockwell Automation Publication 1502-UM052H-EN-P - June 2013

Chapter 4

Maintenance

Table 5 - Altitude Range Spring Requirements, 400A Mechanical (relay control only)

Altitude Range

Spring Part No.

Color Code

Continuous
Current Rating

B.I.L. Rating

0...1000 m

80153-567-01

Bronze

400 A

60 kV

1000...2000 m

80026-007-02

Green

390 A

54 kV

2000...3000 m

80026-008-02

Blue

380 A

48 kV

3000...4000 m

80026-009-02

Black

370 A

42 kV

4000...5000 m

80026-010-02

Olive

360 A

36 kV

IMPORTANT

A contactor will only function properly in the altitude range for which it is set
up. If functional tests are required, they must be performed at the proper
altitude or in a pressure chamber which simulates the proper altitude.