Mechanically latched contactor set-up procedure – Rockwell Automation 1502 Medium Voltage 400A Contactor - Series E User Manual

Page 52

Advertising
background image

52

Rockwell Automation Publication 1502-UM052H-EN-P - June 2013

Chapter 4

Maintenance

Mechanically Latched
Contactor Set-up Procedure

1. The overtravel, contact gap and auxiliary set-up procedures are the same

for mechanically latched contactors as they are for electrically held
contactors except that instead of energizing the contactor with the
“TEST” circuit, the contactor must be held closed mechanically by means
of a clamp or special fixture as shown in Figure 4.25. It is important that
the contactor is held closed tightly with the armature against the magnet
cores when gauging the overtravel, contact gap and auxiliary positioning.
Allen-Bradley part number 80154-149-51 is recommended, however, a C-
clamp can be used at the rear of the contactor to pull up the actuator plate
(care must be taken not to overtighten the C-clamp and bend the actuator
plate).

Figure 49 - Clamping a Mechanically Latched Contactor Closed

2. Clamp the contactor closed as detailed in Step 1. The latch mechanism

should be in place with the mounting bolts loose enough to allow sliding
along the adjustment slots.

3. With the contactor lying on its back, insert a .015 in. (0.38) feeler gauge

between the latch roller and the armature plate as shown in

Figure 50

.

Tighten the mounting blots (do not overtorque 1/4 inch nuts or 5/16 in
bolts).

Figure 50 - Gauging Mechanical Latch Location

Mechanically Latched
Contactor Clamping Fixture

0.010 in. [0.25 mm]

Insert feeler gauge here

Advertising