Publication 1413-UM001C-EN-P - May 2006

Installation 19

3. Connect 120V ac control power and earth ground.

4. Install the Ethernet interface module (9) within 45 cm (18 in.) of

the Channel 0 connector on the MicroLogix 1500 controller (1).

5. Verify that the DC Source switch on the Ethernet interface

module is in the Cable position.

6. Connect the cable (11) between Channel 0 of the MicroLogix

1500 controller and the Ethernet interface module.

7. Connect the PanelView 550 terminal to the Ethernet interface

module using the Ethernet crossover cable (12) if the system will
not be connected to a local area network.

8. Connect both the PanelView 550 terminal and the Ethernet

interface module to the Ethernet local area network via a
suitable hub or switch using user-provided CAT5 Ethernet cables
if the system will be connected to a local area network.

L1

L2

White

(Neutral)

Green

(Earth Ground)

L1

L2

Black (Line)

Brown (Line)

Green

(Earth Ground)

Green/Yellow

(Protective Earth)

Blue

(Neutral)

120/240V ac, 3 Wire,

U.S. Color Code

120/240V ac,

3 Wire, European

Harmonized Color Code

Power Terminal Block (fixed)

To Power Source

To Power Source

GND

GND

ETHERNET

FAULT

RS232

NET

TX/RX

TX/RX

PWR

CABLE

EXTERNAL

IP

To Ethernet LAN