5 - add special functionality, Pfmgr4 logic, Chapter 5 – Rockwell Automation 1413-ME-PEA Capacitor Bank Controller - Series B User Manual

Page 53: Add special functionality, Overview, Chapter

Advertising
background image

51

Publication 1413-UM001C-EN-P - May 2006

Chapter

5

Add Special Functionality

For added functionality, custom ladder-logic programming and
hardware integration are permitted, however, strict guidelines must be
followed to comply with warranty contracts.

• Altering of existing ladder-logic code is prohibited and will void

all warranty contracts.

• Additional functionality can only be implemented by adding

additional ladder logic code to subroutine PFMGR4.

• Additional subroutines may be written, but must be called

through PFMGR4.

PFMGR4 Logic

The following sections provide details of PFMGR4 ladder-logic
programming.

Overview

There are three basic sections to PFMGR4:

• Power factor alarm

The power-factor alarming section specifies whether your
system KVAR is within its specified range and how long to wait
before alarming when it is out of range.

• Step control

The step control section specifies when to actuate or trip a step.

• Step routine

The step routine section specifies what step should be actuated
or tripped.