Parameter descriptions – Rockwell Automation 1413-ME-PEA Capacitor Bank Controller - Series B User Manual

Page 26

Advertising
background image

Publication 1413-UM001C-EN-P - May 2006

24 Installation

Parameter Descriptions

Wiring mode – selected to match the physical connections to

the power system

Delta 3 CT

Delta 2 CT

Direct delta 3 CT

Direct delta 2 CT

Open delta 3 CT

Open delta 2 CT

Wye (default)

Single phase

PT (VT) primary voltage – reflects the voltage rating on the

high side of the potential/voltage transformers. Range
1…10,000,000 V, default 480

PT (VT) secondary voltage – reflects the voltage rating on the

low side of the potential/voltage transformers. Range 1…600 V,
default 480

CT primary current – reflects the current rating on the high

side of the phase current transformers. Range 1…10,000,000 A,
default 5. The CT secondary current is also adjustable but the
default value of 5 A is standard

I4 primary current – reflects the current rating on the high

side of the neutral current transformer. Range and defaults are
the same as CT primary current setting

RS-485 node number – sets the communications address on

the RS-485 network to the MicroLogix 1500 controller.
Factory-set at 101 for PM 1, must be user configured for optional
PMs 2 …4. Range 1…247, default is the Unit ID

IP address, subnet mask, default gateway – Ethernet port

settings required for communications with the user’s local area
network

Set Parameters with the Powermonitor Display Module

The Basic Configuration table contains the configuration parameters
needed for initial setup of the Powermonitor meter in the base system.

The table and diagram below describe the basic functionality of the
Powermonitor display module.