Powermonitor meter configuration – Rockwell Automation 1413-ME-PEA Capacitor Bank Controller - Series B User Manual

Page 25

Advertising
background image

Publication 1413-UM001C-EN-P - May 2006

Installation 23

Powermonitor meter communications settings are changed using the
Powermonitor display module.

Please refer to Powermonitor Meter Configuration Parameters table.

Powermonitor Meter
Configuration

The table below lists the configuration parameters that must be set up
for correct operation of the capacitor bank controller.

For additional information regarding Powermonitor meter
configuration, please refer to the Powermonitor 3000 User Manual,
publication 1404-UM001.

Powermonitor Ethernet Communication Settings

Device / Parameter

Powermonitor Meter 2

Powermonitor Meter 3

Powermonitor Meter 4

Node Address

102

103

104

IP Address

(1)

192.168.0.UnitID

192.168.0.UnitID

192.168.0.UnitID

Subnet Mask

255.255.255.0

255.255.255.0

255.255.255.0

Default Gateway

192.168.0.1

192.168.0.1

192.168.0.1

(1)

The Unit ID is listed on the Powermonitor nameplate.

Powermonitor Meter Configuration Parameters

Parameter

PM 1

PM 2

(4)

PM 3

(4)

PM 4

(4)

Wiring mode

(1)

PT (VT) primary voltage

PT (VT) secondary voltage

CT primary current

I4 primary current

RS-485 node number

101

(3)

102

103

104

IP address

(2)

192.168.0.101

Subnet mask

(2)

255.255.255.0

Default gateway address

(2)

192.168.0.1

(1)

Wiring mode must be Wye when using NEU or Retro CTPT mode.

(2)

Applies only to Ethernet Powermonitor meter options.

(3)

Default factory setting for base unit.

(4)

Optional additional Powermonitor meters.