N7:43

Control
Word

(1)

This is the control word for the capacitor bank
controller. The first three (3) bits of the control
word is used to set the CTPT Mode. Bit 4 is used
to initiate a restore of factory defaults. This
should be treated as a momentary state. Bit 5 is
used to initiate the step size buffer. This bit should
also be treated as a momentary state. Bit 6 is
used for disabling step tolerance. The BCD value
for each bit is available for easy setup.

Examples

- CTPT Mode 2 and Disable Step Tolerance = 68

- CTPT Mode 0 and Restore Factory Defaults = 17
to initiate a restore, then 1.

- CTPT Mode 1 and Initiate Step Buffer = 34 to
initiate step buffer, then 2

43

Ext
Configuration
2

N7:44

Unbalance
Alarm Time

seco
nds

The amount of time before alarming and resetting
the Unbalance Alarm flag

44

Ext
Configuration
1

N7:45

Number of
Powermonit
or meters

The number of Powermonitor meters to include in
the aggregate kW and kVAR calculations

45

Configuration

N7:46

Number of
Capacitor
Steps

The number of capacitor steps to be controlled

46

Configuration

N7:47

Operating
Mode

The operating mode:

0 - Manual

1 - Linear

2 - Balanced

3 - Best Fit

4 - User Defined

5 - % Voltage THD

47

Configuration

N7:59

Number of
Samples

The number of kVAR samples to average together
when auto-configuring capacitor step sizes.

1 - 10

5

-

Ext
Configuration
1

(1)

Please see the Control Word table.

Control and Status Parameters

Address

Parameter

Unit

Description

Range

Default

DAT
INT

PanelView
Screen

Control Word

Bit

Parameter

BCD Value

0

CTPT Mode 0 - Normal

1

1

CTPT Mode 1 - Neutral

2

2

CTPT Mode 2 - Retro

4

3

8