User variables – Rockwell Automation 1413-ME-PEA Capacitor Bank Controller - Series B User Manual

Page 57

Advertising
background image

Publication 1413-UM001C-EN-P - May 2006

Add Special Functionality 55

User Variables

This chart displays a list of data points and their access rights for use
in your custom code.

User-defined Variables

Symbol

Datapoint

Description

Datatype

Units

Access
Privilege

System Status

PF_leading

B3/.102

This flag indicates the power factor is leading.

Bit

Read

PF_lagging

B3/.103

This flag indicates the power factor is lagging.

Bit

Read

Bus_Net_PF

F8:00

This register holds the total power factor on the monitored
bus.

Float

Read

Bus_Net_KW

F8:01

This register holds the total real power on the monitored
bus.

Float

W

Read

Bus_Net_KVAR

F8:02

This register holds the total reactive power on the
monitored bus.

Float

kVAR

Read

Bus_Volts

F8:15

This register holds the three-phase average line-to-line
voltage as measured by the first Powermonitor meter.

Float

V

Read

Net_Current

F8:16

This register holds the net current obtained from the
Powermonitor meter.

Float

A

Read

%THD_V

F8:17

This register holds the % total harmonic-distortion voltage
as measured by the first Powermonitor meter.

Float

Read

KVAR_Lead_DB

N7:34

Leading kVAR dead-band limit, typically 33% of smallest
step.

Int

Read

KVAR_Lag_DB

N7:35

Lagging kVAR dead-band limit, typically 66% of largest
step.

Int

Read

PF_inRange_ Timer_4

T93:0

Time to wait for PF to come into acceptable range, before
alarming.

Timer

Read

Step Status

Open_1

B3/00

This flag indicates that Contactor #1 has been activated. (0
= Open, 1 = Active)

Bit

Read

Open_2

B3/01

This flag indicates that Contactor #2 has been activated. (0
= Open, 1 = Active)

Bit

Read

Open_3

B3/02

This flag indicates that Contactor #3 has been activated. (0
= Open, 1 = Active)

Bit

Read

Open_4

B3/03

This flag indicates that Contactor #4 has been activated. (0
= Open, 1 = Active)

Bit

Read

Open_5

B3/04

This flag indicates that Contactor #5 has been activated. (0
= Open, 1 = Active)

Bit

Read

Open_6

B3/05

This flag indicates that Contactor #6 has been activated. (0
= Open, 1 = Active)

Bit

Read

Open_7

B3/06

This flag indicates that Contactor #7 has been activated. (0
= Open, 1 = Active)

Bit

Read