Introduction

1-7

In parameter 81 (Non-Configurable Fault Status), bit 5 Master/ Slave
Cable Loss and bit 6 Master Slave Enable Timeout are specific to the
Master/Slave drives. Faults specific to the Master/Slave drives and
their probable causes are covered in greater depth in Chapter 4,
Troubleshooting.

Specifications

Specifications for the Master/Slave version of the 1336 FORCE drive
match those of standalone units in the the areas of:

Control Specs (see publication1336 FORCE 5.12)

Options (see publication 1336 FORCE 5.12)

Standard Features (see publication 1336 FORCE 5.12)

Options (see publication 1336 FORCE 5.12)

Protective Features (see publication 1336 FORCE 5.12)

Environmental Specifications (see publication 1336 FORCE
5.12)

Feedback Devices (see publication 1336 FORCE 5.12)

Areas where the Master/Slave version differs from the standard
FORCE drive include:

Electrical Specifications -

Input Voltage Rating: 380 - 575V (G & H Frame Drives), 3
Phase, +10%, -15% nominal

Input Power Rating: 4-1110 KVA (460V)

4-1156 KVA (500V)

6-1388 KVA (600V)

Input Frequency: 50/60Hz (+/- 3Hz)

Standard Output Voltage: Each frame size is line dependent and
can power a motor between the following voltages:

G Frame -380 - 480 VAC (line dependent)

500 - 600 VAC (line dependent)

H Frame - 500 - 600 VAC (line dependent)

Output Current: 5-1346A

Output Power: 4 - 380 KVA (380 V)

4 - 416 KVA (415V)

4 - 1074 KVA (460V)

4 - 1342 KVA (575V)

Output Horse Power (Continuous): 1000 - 1600 HP

Overload Capability: 100% Fundamental current (each
standalone inverter)

1 minute - 150% (each standalone inverter)

For example: While the overload capability of the M/S drive does
not exceed 150%, it could be viewed as having a 1 minute
overload capability, as each drive is capable of 150% for 1 min.