Test points – Rockwell Automation 1336T Master/Slave Parallel AC Drv User Manual

Page 42

Advertising
background image

1336 FORCE-5.19 – August, 2000

4-4

Troubleshooting

Test Points

The Hardware testpoints on both the Main Control Board and the
PLC Comm Board for both the Master and Slave drives remain the
same as for standalone units. The expected output from each testpoint
is as follows:

Main Control Board Test Points

TestPoint

Application

TP1

DGND

TP2

+5V

TP3

+15V

TP4

AGND

TP5

-15V

TP6

-2.5 to 2.5V

TP7

0 to 2.5V

TP8

+5V when faulted

TP9

CHA Encoder Fdbk 0 to 5 Square Wave with respect to TP1 or TP25 DGND

TP10

Reserved

TP11

Square Wave (Follows Carrier Frequency)

TP12

Reserved

TP13

CHB Encoder Fdbk 0 to 5V Square Wave with respect to TP1 or Tp25 DGND

TP14

Bus Voltage FDBK (4V = 650 vdc)

TP15

Feed Forward Voltage (0 to +/- 7.5V sine wave)

TP16

Ia FDBK (0 to = +/-5V sine wave) same as Iq feedback

TP17

Ic FDBK (0 to = +/-5V sine wave) same as Iq feedback

TP18

Iqs Command (0 to +/- 10V sine wave)

TP19

Ids Command (0 to +/-5V sine wave)

TP20

Master Reset (5V = Reset)

TP21

Id FDBK (0 to +/- 5V sine wave)

TP22

Feed Forward Voltage (0 to +/- 7.5V sine wave)

TP23

ISO 12V for Tachometer/Encoder

TP24

ISO RTN for Tachometer/Encoder

TP25

DGND