1336 FORCE-5.19 – August, 2000

Mounting and Wiring Your 1336 FORCE Master/Slave Drive

2-5

Check the motor connections provided by the vendor. Match
motor phasing and motor terminal connections for both the
master and slave drives. The Reliance motor shown in the
following example matches T1-T11, T2-T22 and T3-T33 for
the motor leads. Corresponding customer connections are L1-
L11, L2 - L22 and L3 - L33.

PLC Requirements

The PLC Must interconnect the faults between the drives. If either
drive faults the PLC should use the external fault in to fault the
other drive. This will decrease the probability that one drive
continues operation if the other faults.

The PLC Must monitor the output current magnitude for both
drives. This is the only way to verify that the drives are sharing
the load. If one of the output fuses opens during operation both
drives should be stopped by the PLC (see parameter 264).

MASTER

SLAVE

T1

T2

T3

MASTER

T11

T22

T33

T1

T2

T3

L1

L2

L3

SLAVE

T11

T22

T33

L11

L22

L33