Understanding Your SLC 500/1746 Control System B-11

This figure shows you how to run ground connections from the chassis to the
ground bus. Two acceptable grounding methods are shown; we recommend
using a ground bus because it reduces the electrical resistance at the
connection.

Master Control Relay

A hard-wired master control relay (supplied by user) provides a convenient
means for emergency shutdown. Since the master control relay allows the
placement of several Emergency-Stop switches in different locations, its
installation is important from a safety standpoint. Overtravel limit switches or
mushroom head push buttons are wired in series so that when any of them
opens, the master control relay is de-energized. This removes power to input
and output device circuits.

ATTENTION

!!!!

Never alter safety circuits to defeat their function, since
serious injury and/or machine damage could result.

2 mm

2

(14 AWG)

2 mm

2

(14 AWG)

2 mm

2

(14 AWG)

5.2 mm

2

(10 AWG)

Preferred Grounding
Method

5.2 mm

2

(10 AWG)

Earth Ground